AS-Interface power supply VAN-24DC-K28

来源:未知    日期:2016/12/19    浏览量:


参数表节选:的技术参数 VAN-24DC-K28

产品阐述
AS-Interface power supply, data decoupling, 4 A, 24 V DC input voltage
General specifications
UL File Number E223176
Indicators/operating means
LED AS-i ok LED green:
ON: AS-Interface voltage OK
OFF: overload or no supply voltage
Electrical specifications
Fusing T10A HBC (not accessible)
Rated operating voltage 24 VDC
18 ... 32,4 VDC (continuous operation)
14 ... 18 VDC (max. 60 s or with derating)
max. 36 VDC (max. continuous input voltage with no damage to the DC/DC converter)
Rated operating current 5.6 A at 24 VDC
Efficiency typ. 90.5 % (24 VDC, 4 A)
Output
Short-circuit protection/overload > 5 A
< 9 A
Current limit > 4.4 A
Current 4 A
Voltage 30.55 VDC ±3 % fixed
Residual ripple < 50 mVSS (500 kHz bandwidth, 50 Ω measurement, with resistive load)
Overvoltage protected max. 36 V
Compliance with standards and directives
Directive conformity  
  EMC Directive 2004/108/EC EN 55022:2006, EN 55011:2009 Class B
EN 61000-6-3:2001 , EN 61204-3:2001
Standard conformity  
  Noise immunity EN 61000-6-2:2005
  Emitted interference EN 61000-6-3:2007
EN 61000-3-2:2010
EN 61000-3-3:2009
  Galvanic isolation IEC 60364-4-41:2005 (PELV)
IEC 60950:1999 (SELV)
  Degree of protection IEC 60529:2001
  Pollution degree EN 60950-1:2006
  Shock and impact resistance EN 60068-2-27:1995
  Vibration resistance EN 60068-2-6:2008
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Note derating
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Pollution degree 2
Mechanical specifications
Degree of protection IP20
Protection class 1 (IEC 60536); Protective conductor connection necessary
Connection Connection terminals, max. conductor cross-section
Flexible cable: 0.5 … 4 mm2
Rigid cable: 0.5 … 6 mm2
Stripping length 7 mm
Mass approx. 500 g
Mounting DIN mounting rail