来源:未知 日期:2017/01/04 浏览量:次
产品阐述 | ||
---|---|---|
Power supply, 24 to 30 V DC, 5 A |
General specifications | ||
---|---|---|
UL File Number | E223176 | |
Functional safety related parameters | ||
MTTFd | 40 a | |
Mission Time (TM) | 10 a | |
Diagnostic Coverage (DC) | 0 % | |
Indicators/operating means | ||
LED Overload |
Red LED lights up for overload, flashes for hiccup mode |
|
LED PWR | LED green | |
Potentiometer | Output voltage adjustment | |
Electrical specifications | ||
Fusing | 3.15 AT | |
Capacity factor | approx. 0.5 (Depending on input voltage) | |
Rated operating voltage |
115/230 VAC Wide range: 90 … 265 VAC |
|
Rated operating current |
2.2 A (115 V) 1.2 A (230 V) |
|
Supply frequency | 47 ... 63 Hz | |
Efficiency | approx. 89 % | |
Output | ||
Current limit | approx. 5.6 A | |
Current | 0 ... 5 A | |
Voltage |
30 V ± 1 % Adjustment range 23 ... 30 V AC |
|
Compliance with standards and directives | ||
Directive conformity | ||
EMC Directive 2004/108/EC and Directive 2000/95/EC |
EN 55011:2009 + A1:2010, EN 61000-6-1:2007, EN 61000-6-2:2005, EN 61000-6-3:2007 + A1:2011, EN 61000-6-4:2007 + A1:2011, EN 61000-3-2:2006 + A1:2009 + A2:2009, EN 61000-3-3:2008 EN 60950-1:2006 + A12:2011 |
|
Standard conformity | ||
Electromagnetic compatibility | EN 55011, EN 61000-6-1, EN 61000-6-2 | |
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -10 ... 70 °C (14 ... 158 °F) with free convection | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Protection class | I, Protective conductor connection necessary | |
Connection |
Connection terminals, max. conductor cross-section 0.5 to 2.5 mm2 Stripping length 5 to 6 mm |
|
Mass | approx. 900 g | |
Mounting | DIN mounting rail |