AS-Interface模块 VAA-4E4A-KE5-ZEJQ/R

来源:未知    日期:2017/03/07    浏览量:


AS-Interface 的主要特性:拓扑机构灵活: 树形,星形,线形等;便于集成到高层总线 (EtherNet/IP, DeviceNet. ProfiNet ….);有支持PLC板卡系列的扫描器;穿刺技术便于安装连接;自动识别替换的子站。

KE系列控制柜模块拥有各种尺寸以及多种不同数量的终端连接。

产品特点:● Housing with push-in connection technology and mechanically coded terminal blocks
              ● Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
              ● Selectable supply to the sensors: External or from the module
              ● Function display for bus, internal sensor supply, inputs, and outputs


产品阐述:
Cabinet module
4 inputs and 4 relay outputs
General specifications:
Slave type Standard slave
AS-Interface specification V3.0
Required master specification ≥ V2.0
UL File Number E223772
Indicators/operating means:
LED FAULT Fault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply
LED INT Internal input supply active; LED green
LED PWR AS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED IN switching state (input); 4 LED yellow
LED OUT Switching state (output); 4 LED yellow
Electrical specifications:
Auxiliary voltage (input) 12 ... 30 V DC PELV
Rated operating voltage 26.5 ... 31.6 V from AS-Interface
Rated operating current ≤ 35 mA (without sensors) / max. 230 mA
Surge protection O1 ... O4: Over voltage category II
UEXT, Ue: overvoltage category II, safe isolated power supplies (PELV)
Input:
Number/Type 4 inputs for 3-wire sensors (PNP), DC
Supply from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage 21 ... 31 V DC (INT)
Current loading capacity ≤ 150 mA, overload- and short-circuit protected (INT)
Input current ≤ 5.6 mA (max.)
Switching point according to DIN EN 61131-2 (type 1)
  0 (unattenuated) ≤ 0.5 mA
  1 (attenuated) ≥ 2 mA
Signal delay < 1 ms (input/AS-Interface)
Output:
Number/Type 4 relay outputs, normally open
Supply none
Nominal load  
  Per contact 2 A/30 VDC; 2 A/250 VAC
For more information, see the "Galvanic Isolation" section
  Per module 8 A
Control circuit ≤ 11 mA per relay (from AS-Interface)
Switching delay < 10 ms (AS-Interface/contact)
Usage category DC-13 and AC-14
Switching  
  Mechanical 5 x 107
  Electrical 2 x 105 (250 VAC, 2 A, cos φ = 0.4)
Galvanic isolation:
Input/Output safe isolation, Rated insulation voltage 252 Veff
Input/AS-Interface Switch position INT: None Switch setting EXT: safe isolation, rated insulation voltage 92 Veff
Output/Output Basic insulation, rated insulation voltage 250 Veff, in phase
Output/AS-Interface safe isolation, Rated insulation voltage 252 Veff
Compliance with standards and directives:
Directive conformity  
  Low Voltage Directive 2006/95/EC EN 60664-1:2007
  EMC Directive 2004/108/EC EN 61000-6-2:2005, EN 61000-6-4:2007, EN 62026:2013
Standard conformity  
  Noise immunity EN 61000-6-2:2005, EN 61326-1:2006, EN 62026:2013
  Emitted interference EN 61000-6-4:2007
  Input EN 61131-2:2004
  Galvanic isolation EN 60664-1:2007
  Degree of protection EN 60529:2000
  Fieldbus standard EN 62026:2013
  Electrical safety IEC 61140:2009
Programming instructions:
Profile S-7.0
IO code 7
ID code 0
ID1 code F
ID2 code E
Data bits (function via AS-Interface) input output
  D0 IN1 O1
  D1 IN2 O2
  D2 IN3 O3
  D3 IN4 O4
Parameter bits (programmable via AS-i) function
  P0 Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
  P1 Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
  P2 Synchronous mode
P2 = 0 synchronous mode on
P2 = 1 synchronous mode off (default settings)
  P3 not used
Ambient conditions:
Ambient temperature -25 ... 60 °C (-13 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Relative humidity 85 % , noncondensing
Climatic conditions For indoor use only
Altitude ≤ 2000 m above MSL
Pollution degree 2
Mechanical specifications:
Degree of protection IP20
Installation in an enclosure with a minimum protection class of IP54 required
Connection Removable push-in terminals
rated connection capacity:
rigid: 0.20 mm2 ... 1.5 mm2
flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2
flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material  
  Housing PA 66-FR
Mass 125 g
Mounting DIN mounting rail