AS-Interface sensor/actuator module VBA-4E4A-KE-ZEJQ/E2L

来源:未知    日期:2017/01/04    浏览量:


参数表节选:的技术参数 VBA-4E4A-KE-ZEJQ/E2L

产品阐述
KE switch cabinet module
4 inputs and 4 outputs
General specifications
Slave type A/B slave
AS-Interface specification V3.0
Required master specification ≥ V3.0
UL File Number E223772
Functional safety related parameters
MTTFd 190 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Indicators/operating means
LED FAULT Error display; red LED
red: communication error, i.e. address is 0
red flashing: overload internal input supply, i.e. overload or lead interruption outputs
LED INT Internal input supply active; LED green
LED PWR AS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED AUX ext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED IN switching state (input); 4 LED yellow
LED OUT switching state (output); 4 LED yellow/red
yellow: output active
red: output overload or lead interruption
Electrical specifications
Auxiliary voltage (input) 12 ... 30 V DC PELV
Auxiliary voltage (output) 20 ... 30 V DC PELV
Rated operating voltage 26.5 ... 31.6 V from AS-Interface
Rated operating current ≤ 35 mA (without sensors) / max. 190 mA
Protection class III
Surge protection UEXT, UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Input
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DC
Supply from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage 21 ... 31 V DC (INT)
Current loading capacity ≤ 150 mA, overload- and short-circuit protected (INT)
Input current ≤ 9 mA (limited internally)
Switching point according to DIN EN 61131-2 (Type 2)
  0 (unattenuated) ≤ 3 mA
  1 (attenuated) ≥ 5 mA
Signal delay < 1 ms (input/AS-Interface)
Output
Number/Type 4 electronic outputs, PNP, overload and short-circuit proof
Supply from external auxiliary voltage UAUX
Current 2 A per output, sum 4A (TB ≤ 40 °C)
0.5 A per output, total 2A (TB ≤ 60 °C, arranged in series without gaps)
2 A per output, total 4A (TB ≤ 60 °C, arranged in series with 5 mm gap)
Voltage ≥ (UAUX - 0.5 V)
Usage category DC-13
Compliance with standards and directives
Directive conformity  
  EMC Directive 2004/108/EC EN 61000-6-2:2005, EN 61000-6-4:2007, EN 50295:1999
Standard conformity  
  Noise immunity EN 61000-6-2:2005, EN 61326-1:2006, EN 50295:1999
  Emitted interference EN 61000-6-4:2007
  Input EN 61131-2:2004
  Degree of protection EN 60529:2000
  Fieldbus standard EN 50295:1999, IEC 62026-2:2006
Programming instructions
Profile S-7.A.7
IO code 7
ID code A
ID1 code 7
ID2 code 7
Data bits (function via AS-Interface) input output
  D0 IN1 O1
  D1 IN2 O2
  D2 IN3 O3
  D3 IN4 O4
Parameter bits (programmable via AS-i) function
  P0 Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
  P1 Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
  P2 Lead breakage outputs
P2 = 0 lead breakage on
P2 = 1 lead breakage off (default settings)
  P3 not used
Ambient conditions
Ambient temperature -25 ... 60 °C (-13 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Relative humidity 85 % , noncondensing
Climatic conditions For indoor use only
Altitude ≤ 2000 m above MSL
Pollution degree 2
Mechanical specifications
Degree of protection IP20
Connection removable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material  
  Housing PA 66-FR
Mass 150 g
Mounting DIN mounting rail
Tightening torque of clamping screws 0.5 Nm ... 0.6 Nm