AS-Interface sensor/actuator module VBA-4E4A-G11-ZAJ/EA2L-F

来源:未知    日期:2017/01/04    浏览量:


参数表节选:的技术参数 VBA-4E4A-G11-ZAJ/EA2L-F

产品阐述
G11 module
4 inputs and 4 outputs
General specifications
Slave type A/B slave
AS-Interface specification V3.0
Required master specification ≥ V3.0
UL File Number E223772
Functional safety related parameters
MTTFd 120 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Indicators/operating means
LED AS-i/FAULT Status display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: sensor supply i.e. overload or lead interruption outputs
LED AUX ext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED IN switching state (input); 4 LED yellow
LED OUT switching state (output); 4 LED yellow/red
yellow: output active
red: output overload or lead interruption
Electrical specifications
Auxiliary voltage (output) 20 ... 30 V DC PELV
Rated operating voltage 18,0 ... 31.6 V from AS-Interface
Rated operating current ≤ 40 mA (without sensors) / max. 240 mA
Protection class III
Surge protection UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DC
option 2 inputs for 4-wire sensors (PNP), DC
Supply from AS-Interface
Voltage 12 ... 31 V
Current loading capacity ≤ 200 mA, overload and short-circuit protected
Input current ≤ 9 mA (limited internally)
Switching point according to DIN EN 61131-2 (Type 2)
  0 (unattenuated) ≤ 3 mA
  1 (attenuated) ≥ 5 mA
Signal delay < 1 ms (input/AS-Interface)
Output
Number/Type 4 electronic outputs, PNP, overload and short-circuit proof
Supply from external auxiliary voltage UAUX
Current 2 A per output
TB ≤ 40 °C: 6 A total
TB ≤ 70 °C: sum O1 + O2 max. 2 A, sum O3 + O4 max. 2 A
Voltage ≥ (UAUX - 0.5 V)
Galvanic isolation
Input/Output safe isolation, rated insulation voltage 40 V DC
Output/AS-Interface safe isolation, rated insulation voltage 40 V DC
Compliance with standards and directives
Directive conformity  
  EMC Directive 2004/108/EC EN 61000-6-2:2005, EN 61000-6-4:2007, EN 50295:1999
Standard conformity  
  Noise immunity EN 61000-6-2:2005, EN 61326-1:2006, EN 50295:1999
  Emitted interference EN 61000-6-4:2007
  Input EN 61131-2:2007
  Degree of protection EN 60529:2000
  Fieldbus standard EN 50295:1999, IEC 62026-2:2006
Programming instructions
Profile S-7.A.7
IO code 7
ID code A
ID1 code 7
ID2 code 7
Data bits (function via AS-Interface) input output
  D0 IN1 O1
  D1 IN2 O2
  D2 IN3 O3
  D3 IN4 O4
Parameter bits (programmable via AS-i) function
  P0 Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
  P1 Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
  P2 Lead breakage outputs
P2 = 0 lead breakage on
P2 = 1 lead breakage off (default settings)
  P3 not used
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Relative humidity 85 % , noncondensing
Climatic conditions For indoor use only
Altitude ≤ 2000 m above MSL
Pollution degree 3
Mechanical specifications
Degree of protection IP68 / IP69K
Connection AS-Interface/UAUX: AS-Interface flat cable
Inputs/outputs: M12 round connector
Material  
  Housing PBT PC
  Mounting screw Stainless steel 1.4305 / AISI 303
Mass 200 g
Tightening torque, housing screws 1.8 Nm
Tightening torque, cable gland 0.4 Nm
Mounting Mounting plate