AS-Interface actuator module VBA-2A-G10-E2L-1M-2V1-W

来源:未知    日期:2017/01/20    浏览量:


参数表节选:的技术参数 VBA-2A-G10-E2L-1M-2V1-W

产品阐述
G10 ultra compact module
2 outputs
General specifications
Slave type A/B slave
AS-Interface specification V3.0
Required master specification ≥ V2.1
UL File Number E223772 "For use in NFPA 79 Applications only"
Functional safety related parameters
MTTFd 516 a
Indicators/operating means
LED FAULT error display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
LED AS-i AS-Interface voltage; LED green
LED OUT Switching state (output); 2 LED yellow
Electrical specifications
Auxiliary voltage 20 ... 30 V DC PELV
Rated operating voltage 18.5 ... 31.6 V from AS-Interface
Rated operating current ≤ 40 mA / max. 60 mA
Protection class III
Surge protection UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Output
Number/Type 2 electronic outputs, PNP, overload and short-circuit proof
Supply from external auxiliary voltage UAUX
Current 2 A per output, TB ≤ 40°C: 4 A total, 40°C < TB ≤ 70°C: 3 A total , overload and short-circuit protected
Voltage ≥ (UAUX - 0.5 V)
Compliance with standards and directives
Directive conformity  
  EMC Directive 2004/108/EC EN 50295:1999
Standard conformity  
  Noise immunity EN 61000-6-2:2005, EN 50295:1999
  Emitted interference EN 61000-6-4:2007
  Degree of protection EN 60529:2000
  Fieldbus standard EN 50295:1999, IEC 62026-2:2008
  Electrical safety IEC 61140:2004
Programming instructions
Profile S-8.A.E
IO code 8
ID code A
ID1 code 7
ID2 code E
Data bits (function via AS-Interface) input output
  D0 - OUT1
  D1 - OUT2
  D2 - -
  D3 - -
Parameter bits (programmable via AS-i) function
  P0 communication monitoring
P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised
P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
  P1 not used
  P2 Lead breakage outputs
P2 = 0 lead breakage on
P2 = 1 lead breakage off (default settings)
  P3 not used
Approvals and certificates
UL approval cULus Listed, Type 1 enclosure
  Maximum permissible ambient temperature max. 65 °C (max. 149 °F)
Ambient conditions
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Degree of protection IP67
IP67 / IP68 / IP69K with flat cable VAZ-FK-S-*
Connection AS-Interface/UAUX: AS-Interface flat cable
Outputs & matching connector: M12 round connector, 4-pin, A-coded, according to IEC 61076-2-101:2012
Material  
  Contacts CuSn / Au
  Housing PBT PC
  Body black PUR
  Cable PUR
  Mounting screw Stainless steel 1.4305 / AISI 303
Cable  
  Sheath diameter ∅4,3 mm
  Color black
  Cores 3 x 0.34 mm2
  Length 1 m
Mass 100 g
Tightening torque, fastening screws 1.65 Nm
Tightening torque, cable gland 0.4 Nm