联系方式
联系人:王经理
 
电 话:021-39520660
 
手  机:15821591180
 
传 真:021-69001586
 
Q    Q:1257746205
 
Email:debon_gk@163.com
 

AS-Interface sensor/actuator module VBA-2E1A-G10-ZAL/E2L-1M-2V1-W

来源:未知    日期:2016/12/19    浏览量:


参数表节选:的技术参数 VBA-2E1A-G10-ZAL/E2L-1M-2V1-W

产品阐述
G10 ultra compact module
2 inputs and 1 output
General specifications
Slave type A/B slave
AS-Interface specification V3.0
Required master specification ≥ V2.1
UL File Number E223772 "For use in NFPA 79 Applications only"
Functional safety related parameters
MTTFd 352 a
Indicators/operating means
LED FAULT error display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
LED AS-i AS-Interface voltage; LED green
LED IN switching state (input); 2 LED yellow
LED OUT Switching state (output); LED yellow
Electrical specifications
Auxiliary voltage 20 ... 30 V DC PELV
Rated operating voltage 18.5 ... 31.6 V from AS-Interface
Rated operating current ≤ 40 mA / max. 60 mA
Protection class III
Surge protection UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type 2 inputs for 2- or 3-wire sensors (PNP), DC
option 1 input for 4-wire sensor (PNP), DC
Supply from external auxiliary voltage UAUX
Voltage 20 ... 30 V
Current loading capacity ≤ 1000 mA overload and short-circuit resistant
Input current ≤ 9 mA (limited internally)
Switching point according to DIN EN 61131-2 (Type 2)
  0 (unattenuated) ≤ 3 mA
  1 (attenuated) ≥ 5 mA
Signal delay < 1 ms (input/AS-Interface)
Output
Number/Type 1 electronic output, PNP,
Supply from external auxiliary voltage UAUX
Voltage ≥ (UAUX - 0.5 V)
Current loading capacity ≤ 1000 mA overload and short-circuit resistant
Compliance with standards and directives
Directive conformity  
  EMC Directive 2004/108/EC EN 50295:1999
Standard conformity  
  Noise immunity EN 61000-6-2:2005, EN 61326-1:2006, EN 50295:1999
  Emitted interference EN 61000-6-4:2007
  Input EN 61131-2:2007
  Degree of protection EN 60529:2000
  Fieldbus standard EN 50295:1999, IEC 62026-2:2006
Programming instructions
Profile S-7.A.E
IO code 7
ID code A
ID1 code 7
ID2 code E
Data bits (function via AS-Interface) input output
  D0 IN1 O1
  D1 IN2 -
  D2 - -
  D3 - -
Parameter bits (programmable via AS-i) function
  P0 communication monitoring
P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised
P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
  P1 Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
  P2 Synchronous mode
P2 = 0 synchronous mode on
P2 = 1 synchronous mode off (default settings)
  P3 not used
Approvals and certificates
UL approval cULus Listed, Type 1 enclosure
  Maximum permissible ambient temperature max. 65 °C (max. 149 °F)
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protection IP67
IP67 / IP68 / IP69K with flat cable VAZ-FK-S-*
Connection AS-Interface/UAUX: AS-Interface flat cable
In-/outputs & matching connector: M12 round connector, 4-pin, A-coded, according to IEC 61076-2-101:2012
Material  
  Contacts CuSn / Au
  Housing PBT PC
  Body black PUR
  Cable PUR
  Mounting screw Stainless steel 1.4305 / AISI 303
Cable  
  Sheath diameter ∅4,3 mm
  Color black
  Cores 4 x 0.34 mm2
  Length 1 m
Mass 100 g
Tightening torque, fastening screws 1.65 Nm
Tightening torque, cable gland 0.4 Nm