来源:未知 日期:2017/12/06 浏览量:次
产品阐述: | ||
---|---|---|
Safety Monitor, 1 integrated safe output |
一般特性: | ||
---|---|---|
AS-Interface specification | V2.1 | |
Switch-on delay | < 10 s | |
Response delay | < 40 ms | |
UL File Number | E198304 | |
功能安全性参数: | ||
Safety Integrity Level (SIL) | SIL 3 | |
Performance level (PL) | PL e | |
MTTFd | 389 a | |
B10d | 2 E+5 | |
指示灯/操作键: | ||
LED green |
Off: contacts of the safety output (OSSD) open constantly lit: contacts of the safety output (OSSD) closed flashing: delay time running for Stop Category 1 |
|
LED yellow |
off: - constantly lit: startup/restart lock active flashing: external test required |
|
LED red |
Off: contacts of the safety output (OSSD) closed constantly lit: contacts of the safety output (OSSD) open flashing: error |
|
LED POWER |
from: no power supply green, continuous illuminated: AS-Interface power supply available |
|
LED AS-i |
from: normal operation red, continuous illuminated: communication error |
|
电气特性: | ||
Rated operating voltage |
24 V DC ± 15 % Residual ripple ≤ 15 % 26.5 ... 31.6 V from AS-Interface |
|
Rated operating current |
≤ 150 mA ≤ 45 mA from AS-Interface |
|
Surge protection |
overvoltage category III for rated operating voltage 300 V DC acc. to VDE 0110 Part 1 |
|
接口: | ||
Interface type | RS 232, serial | |
Transfer rate | 9600 baud, no parity, 1 start bit, 1 stop bit, 8 data bits | |
输入: | ||
Number/Type | 2 opto-coupling inputs (high-active) "Start" and "protection control (EDM)", input currents about 10 mA at 24 V DC | |
输出: | ||
Safety output |
2 potential-free NO contacts, max. contact loading: 1 A DC-13 at 24 V DC, 3 A AC-15 at 230 V AC |
|
Output type |
Signal output: PNP transistor output, 200 mA, short-circuit and reverse-polarity-proof |
|
与标准和规范体系的一致性: | ||
Directive conformity | ||
Machinery Directive 2006/42/EC | EN 954-1:1996, EN 61496:2005, EN 60204-1:2006 | |
Low Voltage Directive 2006/95/EC | EN 60947-5-1:2005 | |
EMC Directive 2004/108/EC | EN 61000-6-2:2006, EN 61000-6-4:2007 | |
Standard conformity | ||
AS-Interface | EN 50295:1999 | |
Functional safety | ISO 13849-1:2008 (up to category 4/PL e), IEC 61508:2000/IEC 62061:2005 (up to SIL3) | |
Electrical safety | EN 50178:1998 | |
周围环境: | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -30 ... 70 °C (-22 ... 158 °F) | |
机械特性: | ||
Degree of protection | IP20 (only for use in electrical operating rooms / switch cabinet suitable with minimum protection type IP54) | |
Connection | screw terminals | |
Material | ||
Housing | Polyamide PA 66 , black | |
Mass | 350 g | |
Mounting | DIN rail mounting |