来源:未知 日期:2017/02/24 浏览量:次
| 产品阐述: | ||
|---|---|---|
| Safety monitor, three 2-channel secure inputs, two secure outputs | ||
| General specifications: | ||
|---|---|---|
| AS-Interface specification | V3.0 | |
| UL File Number | E223772 | |
| Functional safety related parameters: | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Performance level (PL) | PL e | |
| Mission Time (TM) | 20 a | |
| PFHd | 5.08 E-9 | |
| Indicators/operating means: | ||
| LED AS-i M |
Status of AS interface master, multicolored LED green: Master OK |
|
| LED SM |
Status of safety monitor, multicolored LED green: Safety monitor OK |
|
| LED S1 ... S6 |
Status of inputs S1 ... S6, yellow LED yellow: Contact open |
|
| LED O1, O2 |
Status of outlputs, multicolored LED yellow: Output on |
|
| Electrical specifications: | ||
| Auxiliary voltage (input) | 20 ... 30 VDC PELV | |
| Insulation voltage | 500 V AS-Interface/UAUX: | |
| Rated operating voltage | 18,0 ... 31.6 V from AS-Interface | |
| Rated operating current |
≤ 200 mA from AS-Interface; ≤ 4 A from AUX |
|
| Interface 1: | ||
| Interface type | Chip card slot | |
| Interface 2: | ||
| Interface type |
RJ-45 socket, 8-pin Ethernet |
|
| Input: | ||
| Number/Type |
6 / 3 safe inputs cat. 4 or 6 standard inputs and outputs |
|
| Supply | 24 V UAUX | |
| Current loading capacity | 10 mA per signal output | |
| Input current | Static switching current: 4 mA at 24 V. Dynamic switching current: 15 mA at 24 V (T=100 μs) | |
| Output: | ||
| Number/Type |
Output circuits 1 and 2 max. contact rating: 700 m ADC-13 at 24 V |
|
| Supply | 24 V UAUX | |
| Compliance with standards and directives: | ||
| Directive conformity | ||
| Machinery Directive 2006/42/EC |
EN 13849-1:2008/AC:2009 EN 62061:2005/A1:2013 |
|
| EMC Directive 2004/108/EC |
EN 62026-2:2013 EN 61000-6-2:2005/AC:2005 EN 61000-6-4:2007/A1:2011 |
|
| Standard conformity | ||
| Electromagnetic compatibility | EN 61326-3-1:2008 | |
| AS-Interface | EN 62026-2:2013 | |
| Functional safety |
EN 61508:2010 and EN 62061:2005 (up to SIL3) EN 13849-1:2008/AC:2009 (PL e) |
|
| Degree of protection | EN 60529:2000 | |
| Programming instructions: | ||
| Profile | configurable | |
| Ambient conditions: | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Mechanical specifications: | ||
| Degree of protection | IP20 | |
| Connection |
removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 |
|
| Material | ||
| Housing | PA 66-FR | |
| Mass | 160 g | |
| Mounting | DIN mounting rail | |
| General information: | ||
| Application areas | Speed monitor: Local inputs, 1 to 2 axles up to 4 kHz | |