AS-Interface安全监视器 VBG-PB-K30-DMD-S16-EV

来源:未知    日期:2017/02/24    浏览量:


● Gateway and safety monitor in one housing
● Connection to PROFIBUS DP
● SafeLink
● Certified up to SIL 3 according to IEC 61508 and EN 62061 and up to PLe according to EN 13849
● 2 AS-Interface networks
● 2 safe output relays and 2 safe electronic outputs
● Integrated data decoupling
● Diagnostics via RJ45 Ethernet port


产品阐述:
Gateway with integrated Safety Monitor
General specifications:
AS-Interface specification V3.0
Duplicate address detection from AS-Interface slaves
Earth fault detection integrated
EMC monitoring integrated
Diagnostics function Extended function via display
Switch-on delay < 10 s
Response delay < 40 ms
UL File Number E223772
Functional safety related parameters:
Safety Integrity Level (SIL) SIL 3
Performance level (PL) PL e
MTTFd 200 a
B10d 2 E+7
Indicators/operating means:
Display Illuminated graphical LC display for addressing and error messages
LED PROFIBUS PROFIBUS master detected; LED green
LED AS-i ACTIVE AS-Interface operation normal; LED green
LED CONFIG ERR configuration error; LED red
LED PRG ENABLE autom. programming; LED green
LED POWER voltage ON; LED green
LED PRJ MODE projecting mode active; LED yellow
LED U AS-i AS-Interface voltage; LED green
LED AUX ext. auxiliary voltage UAUX ; LED green
LED EDM/Start External device monitoring circuit inputs closed, 4x yellow LEDs
LED output circuit Output circuit closed; 4 x green LEDs
Button 4
Electrical specifications:
Insulation voltage ≥ 500 V
Rated operating voltage 26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V DC
Rated operating current ≤ 300 mA off AS interface network 1
≤ 70 mA off AS interface network 2
Interface 1:
Interface type RS-485
Protocol PROFIBUS DP V1
Transfer rate 9.6 kBit/s / 12 MBit/s , Automatic baud rate detection
Interface 2:
Interface type Ethernet: RJ-45
Diagnostic Interface
Interface 3:
Interface type Chip card slot
Input:
Number/Type 4 EDM/Start inputs:
EDM: Inputs for the external device monitoring circuits
Start: start inputs:
Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs)
Output:
Safety output Output circuits 1 and 2: 2 potential-free contacts,
max. contact load:
3  ADC-13 at 30 VDC,
3 AAC-15 at 30 VAC
Output circuits 3 and 4: 2 PNP transistor outputs
max. contact load:
0.5  ADC-13 at 30  VDC
Connection:
PROFIBUS Sub-D interface
AS-Interface spring terminals, removable
Compliance with standards and directives:
Directive conformity  
  EMC Directive 2004/108/EC EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity  
  Electromagnetic compatibility EN 61000-6-2:2005, EN 61000-6-4:2007
  AS-Interface EN 50295:1999
  Degree of protection EN 60529:2000
  Shock and impact resistance EN 61131-2:2004
  Fieldbus standard PROFIBUS according to DIN 19245 Part 3
Ambient conditions:
Ambient temperature 0 ... 55 °C (32 ... 131 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications:
Degree of protection IP20
Material  
  Housing Stainless steel
Mass 800 g
Construction type Low profile housing , Stainless steel