AS-Interface电源 VAN-230/500AC-K24

来源:未知    日期:2017/02/09    浏览量:


● 8 A output load
● 200 ... 500 VAC
● SELV
● LED operating display
● AS-Interface data decoupling
● Power factor correction


产品阐述:
AS-Interface power supply, data decoupling, 8 A
Functional safety related parameters:
MTTFd 40 a
Mission Time (TM) 10 a
Diagnostic Coverage (DC) 0 %
Indicators/operating means:
LED Overload Red LED
lights up for overload, flashes for hiccup mode
LED PWR LED green
Electrical specifications:
Fusing 1.6 AT
Capacity factor 0.7 Capacitive at 400 VAC
Rated operating voltage 195 ... 500 V AC
Rated operating current 1 A at 400 VAC
Supply frequency 47 ... 63 Hz
Efficiency 87 %
Nominal voltage 230/400 VAC
Output:
Current limit approx. 8.5 A
Current 8 A
Voltage 31.2 V ±1 % 
Compliance with standards and directives:
Directive conformity  
  EMC Directive 2004/108/EC EN 50083-2:2006
Standard conformity  
  Noise immunity EN 61000-6-1:2007, EN 61000-6-2:2005
  AS-Interface IEC 62026-2:2006
Ambient conditions:
Ambient temperature -10 ... 40 °C (14 ... 104 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications:
Degree of protection IP20
Protection class I, Protective conductor connection necessary
Connection Connection terminals, max. conductor cross-section
0.5  to  2.5 mm2
Stripping length 5  to  6 mm
Mass approx. 1200 g