来源:未知 日期:2017/02/09 浏览量:次
| 产品阐述: | ||
|---|---|---|
| AS-Interface power supply, data decoupling, 8 A | ||
| Functional safety related parameters: | ||
|---|---|---|
| MTTFd | 40 a | |
| Mission Time (TM) | 10 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Indicators/operating means: | ||
| LED Overload |
Red LED lights up for overload, flashes for hiccup mode |
|
| LED PWR | LED green | |
| Electrical specifications: | ||
| Fusing | 1.6 AT | |
| Capacity factor | 0.7 Capacitive at 400 VAC | |
| Rated operating voltage | 195 ... 500 V AC | |
| Rated operating current | 1 A at 400 VAC | |
| Supply frequency | 47 ... 63 Hz | |
| Efficiency | 87 % | |
| Nominal voltage | 230/400 VAC | |
| Output: | ||
| Current limit | approx. 8.5 A | |
| Current | 8 A | |
| Voltage | 31.2 V ±1 % | |
| Compliance with standards and directives: | ||
| Directive conformity | ||
| EMC Directive 2004/108/EC | EN 50083-2:2006 | |
| Standard conformity | ||
| Noise immunity | EN 61000-6-1:2007, EN 61000-6-2:2005 | |
| AS-Interface | IEC 62026-2:2006 | |
| Ambient conditions: | ||
| Ambient temperature | -10 ... 40 °C (14 ... 104 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Mechanical specifications: | ||
| Degree of protection | IP20 | |
| Protection class | I, Protective conductor connection necessary | |
| Connection |
Connection terminals, max. conductor cross-section 0.5 to 2.5 mm2 Stripping length 5 to 6 mm |
|
| Mass | approx. 1200 g | |
| Mounting | DIN mounting rail | |