来源:未知 日期:2017/01/20 浏览量:次
| 产品阐述 | ||
|---|---|---|
| AS-Interface power supply, data decoupling, 2,8 A | ||
| General specifications | ||
|---|---|---|
| UL File Number | E223176 | |
| Indicators/operating means | ||
| LED AS-i ok |
LED green: ON: AS-Interface voltage OK OFF: overload or no supply voltage |
|
| Electrical specifications | ||
| Fusing | 2.5 AT (not replacable) | |
| Capacity factor | > 0.5 | |
| Rated operating voltage |
nominal: 100 ... 120 VAC/220 ... 240 VAC permissible: 85 ... 132 VAC/184 ... 264 VAC |
|
| Rated operating current |
2.0 A at 115 VAC 0.9 A at 230 VAC |
|
| Supply frequency | 47 ... 63 Hz | |
| Efficiency | 90.5 % (230 VAC, 2.8 A) | |
| Output | ||
| Current limit | > 3.2 A | |
| Current | 2.8 A | |
| Voltage | 30.55 VDC ± 3 % fixed | |
| Residual ripple | ≤ 50 mVss (500 kHz bandwidth, 50-Ω-measurement with ohmic load) | |
| Short-circuit current | min. 3.2 A, max. 4.6 A | |
| Compliance with standards and directives | ||
| Directive conformity | ||
| Low Voltage Directive 2006/95/EC | EN 60950-1:2006, EN 61204-3:2001 | |
| EMC Directive 2004/108/EC | EN 61000-6-2:2005, EN 61000-6-3:2007, EN 50295:1999 | |
| Standard conformity | ||
| Electromagnetic compatibility | EN 61000-6-2:2005; EN 61000-6-3:2007 | |
| AS-Interface | EN 50295:1999, IEC 62026-2:2006 | |
| Mech. capacity | EN 60068-2-6:2008 | |
| Shock and impact resistance | EN 60068-2-27:1995 | |
| Ambient conditions | ||
| Ambient temperature | -10 ... 70 °C (14 ... 158 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Pollution degree | 2 (EN 60950) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Protection class | I, Protective conductor connection necessary | |
| Connection | Connection terminals, max. conductor cross-section 0.5 ... 6 mm2 (20-10 AWG), Stripping length 7 mm | |
| Mass | approx. 500 g | |
| Mounting | DIN mounting rail | |