来源:未知 日期:2017/12/19 浏览量:次
产品阐述: | ||
---|---|---|
G11 analog module 2 analog inputs |
一般特性: | ||
---|---|---|
Slave type | Standard slave | |
AS-Interface specification | V3.0 | |
Required master specification | ≥ V2.1 | |
UL File Number | E223772 | |
功能安全性参数: | ||
MTTFd | 190 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
指示灯/操作键: | ||
LED AS-i/FAULT |
Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
|
LED ANALOG |
status of input signal; LED yellow off: not active on: signal within measurement range flashing: signal outside of measurement range |
|
LED AUX |
ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
|
LED INT/EXT |
status display input supply; LED green green: input supply from AS-Interface off: input supply from auxiliary voltage |
|
电气特性: | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 60 mA (without sensors) / max. 200 mA | |
Protection class | III | |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) | |
输入: | ||
Number/Type |
2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V Pt100: -200 ... 850 °C |
|
Supply | from AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT) | |
Current loading capacity |
≤ 140 mA from AS-Interface; overload and short-circuit resistant ≤ 600 mA from external auxiliary voltage UAUX , overload and short-circuit protected |
|
Input resistance |
current input: max. 70 Ω voltage input: 100 kΩ |
|
Measuring current | for Pt100: approx. 1 mA | |
Accuracy |
Voltage/current: 0.1% of accumulated value Pt100: 0.1% of indicated temperature [°C] + 0.3 °C |
|
Resolution |
16 Bit / 1 µA (current input) or 16 bit / 1 mV (voltage input) or 16 Bit / 0.1°C (temperature input) |
|
Temperature influence |
Voltage/current: 20 ppm/K Pt100: (10 ppm of indicated temperature [°C] + 0.003 °C)/K |
|
与标准和规范体系的一致性: | ||
Directive conformity | ||
EMC Directive 2004/108/EC | EN 50295:1999 | |
Standard conformity | ||
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, IEC 62026-2:2008 | |
Emitted interference | EN 61000-6-4:2007 | |
Input | EN 61131-2:2007 | |
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 50295:1999, IEC 62026-2:2008 | |
编程指令: | ||
Profile | S-7.3.D | |
IO code | 7 | |
ID code | 3 | |
ID1 code | F | |
ID2 code | D | |
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. | |
Parameter bits (programmable via AS-i) | function | |
P0 |
50/60 Hz filter P0=1, enabled P0=0, disabled |
|
P1 |
projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected |
|
P2 |
Indication of the peripheral fault by exceeding measuring range P2=1, peripheral fault is reported P2=0, peripheral fault is not reported |
|
P3 |
P3=1, normal operating mode P3=0, both channels in current mode and without recognition of wire breakage |
|
周围环境: | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Pollution degree | 3 | |
机械特性: | ||
Degree of protection | IP68 / IP69K | |
Connection |
AS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black Inputs: M12 round connector |
|
Material | ||
Housing | PBT PC | |
Mounting screw | Stainless steel 1.4305 / AISI 303 | |
Mass | 200 g | |
Tightening torque, housing screws | 1.8 Nm | |
Tightening torque, cable gland | 0.4 Nm | |
Mounting | Mounting plate |