来源:未知 日期:2016/12/30 浏览量:次
| 产品阐述 | ||
|---|---|---|
| Gateway with integrated Safety Monitor | ||
| General specifications | ||
|---|---|---|
| AS-Interface specification | V3.0 | |
| Duplicate address detection | from AS-Interface slaves | |
| Earth fault detection | integrated | |
| EMC monitoring | integrated | |
| Diagnostics function | Extended function via display | |
| Switch-on delay | < 10 s | |
| Response delay | < 40 ms | |
| UL File Number | E223772 | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Performance level (PL) | PL e | |
| MTTFd | 200 a | |
| B10d | 2 E+7 | |
| Indicators/operating means | ||
| Display | Illuminated graphical LC display for addressing and error messages | |
| LED PROFIBUS | PROFIBUS master detected; LED green | |
| LED AS-i ACTIVE | AS-Interface operation normal; LED green | |
| LED CONFIG ERR | configuration error; LED red | |
| LED PRG ENABLE | autom. programming; LED green | |
| LED POWER | voltage ON; LED green | |
| LED PRJ MODE | projecting mode active; LED yellow | |
| LED U AS-i | AS-Interface voltage; LED green | |
| LED AUX | ext. auxiliary voltage UAUX ; LED green | |
| LED EDM/Start | External device monitoring circuit inputs closed, 4x yellow LEDs | |
| LED output circuit | Output circuit closed; 4 x green LEDs | |
| Button | 4 | |
| Electrical specifications | ||
| Insulation voltage | ≥ 500 V | |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V DC | |
| Rated operating current |
≤ 300 mA off AS interface network 1 ≤ 70 mA off AS interface network 2 |
|
| Interface 1 | ||
| Interface type | RS-485 | |
| Protocol | PROFIBUS DP V1 | |
| Transfer rate | 9.6 kBit/s / 12 MBit/s , Automatic baud rate detection | |
| Interface 2 | ||
| Interface type |
Ethernet: RJ-45 Diagnostic Interface |
|
| Interface 3 | ||
| Interface type | Chip card slot | |
| Input | ||
| Number/Type |
4 EDM/Start inputs: EDM: Inputs for the external device monitoring circuits Start: start inputs: Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs) |
|
| Output | ||
| Safety output |
Output circuits 1 and 2: 2 potential-free contacts, max. contact load: 3 ADC-13 at 30 VDC, 3 AAC-15 at 30 VAC Output circuits 3 and 4: 2 PNP transistor outputs max. contact load: 0.5 ADC-13 at 30 VDC |
|
| Connection | ||
| PROFIBUS | Sub-D interface | |
| AS-Interface | spring terminals, removable | |
| Compliance with standards and directives | ||
| Directive conformity | ||
| EMC Directive 2004/108/EC | EN 61000-6-2:2005, EN 61000-6-4:2007 | |
| Standard conformity | ||
| Electromagnetic compatibility | EN 61000-6-2:2005, EN 61000-6-4:2007 | |
| AS-Interface | EN 50295:1999 | |
| Degree of protection | EN 60529:2000 | |
| Shock and impact resistance | EN 61131-2:2004 | |
| Fieldbus standard | PROFIBUS according to DIN 19245 Part 3 | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Material | ||
| Housing | Stainless steel | |
| Mass | 800 g | |
| Construction type | Low profile housing , Stainless steel | |