General specifications | ||
---|---|---|
Sensing range | 100 ... 300 mm | |
Standard target plate | 100 mm x 100 mm | |
Transducer frequency | approx. 255 kHz | |
Electrical specifications | ||
Operating voltage | 10 ... 30 V DC , ripple 10 %SS | |
No-load supply current | ≤ 20 mA | |
Input | ||
Input type |
1 program input [receiver] switch point 1: -UB ... +1 V, switch point 2: +6 V ... +UB input impedance: > 4.7 kΩ pulse duration: ≥ 1 s 1 test input [emitter] emitter deactivated: +6 V ... +UB input impedance: > 4.7 kΩ |
|
Output | ||
Output type | PNP, NO | |
Rated operating current | 200 mA , short-circuit/overload protected | |
Voltage drop | ≤ 3 V | |
Switch-on delay | < 5 ms | |
Switching frequency | ≤ 100 Hz | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated ≤36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Connection type | Connector M12 x 1 , 4-pin | |
Degree of protection | IP68 / IP69K | |
Material | ||
Housing |
Stainless steel 1.4435 / AISI 316L O-ring for cover sealing: EPDM |
|
Transducer | PTFE (diaphragm surface) | |
Mass | 25 g |