通用输入输出模块 LB7104A

来源:未知    日期:2017/02/20    浏览量:


● 4-channel
● Inputs Ex ia, Outputs Ex ia
● Installation in Zone 2, Div. 2 or safe area
● Analog input, digital input,
● analog output, digital output
● Supply circuit 15 V (20 mA)
● HART communication via field bus or service bus
● Simulation mode for service operations (forcing)
● Line fault detection (LFD): one LED per channel
● Permanently self-monitoring
● Module can be exchanged under voltage


Supply:
Connection backplane bus
Rated voltage 12 V DC , only in connection with the power supplies LB9***
Power dissipation 1.5 W
Power consumption 3 W
Internal bus:
Connection backplane bus
Interface manufacturer-specific bus to standard com unit
Input:
Number of channels 4
Connection Analog input (HART) : terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Digital Input : terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Output:
Number of channels 4
Connection Analog output (HART) : terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Digital Output : terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Watchdog output off 0.5 s after serious fault
Analog input:
Suitable field devices transmitters for pressure, differential pressure, level, flow, temperature, etc.
Transmitter supply voltage 15 V at 20 mA
Line fault detection can be switched on/off for each channel via configuration tool , configurable via configuration tool
  Short-circuit Ex works settings: > 21 mA configurable between 0 ... 26 mA
  Open-circuit Ex works settings: < 3.6 mA configurable between 0 ... 26 mA
Analog output:
Suitable field devices proportional valves , I/P converters , local indicators
Line fault detection can be switched on/off for each channel via configuration tool , configurable via configuration tool
  Short-circuit Ex works settings: < 50 Ω configurable between 0 ... 26 mA
  Open-circuit deviation of preset output value > 0.5 mA
Load 750 Ω max.
Digital input:
Suitable field devices mech. contacts or optocouplers
Switching point: OFF < 1.2 mA
Switching point: ON > 2.1 mA
Line fault detection can be switched on/off for each channel via configuration tool
  Connection mechanical switch with additional resistors (see connection diagram)
  Short-circuit > 7 mA
  Open-circuit < 0.1 mA
Digital output:
Suitable field devices solenoid valves, acoustic alarms and LED indicators (line fault detection can be deactivated)
Drive capability 12 V / 25 mA
Open loop voltage min. 22.7 V
Current limit 26 mA
Line fault detection can be switched on/off for each channel via configuration tool
  Test current 0.4 mA
  Short-circuit < 50 Ω
  Open-circuit < 0.2 mA
Internal resistance 385 Ω
Transfer characteristics:
Deviation 0.1 % of the signal range at 20 °C (68 °F)
Refresh time approx. 100 ms (4 channels)
Indicators/settings:
LED indicator Power LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1)
Configuration LED (AI, AO, DI, DO) white: selected channel mode
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2006
Conformity:
Electromagnetic compatibility NE 21:2007
Degree of protection IEC 60529:2000
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Shock resistance shock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistance frequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications:
Degree of protection IP20 when mounted on backplane
Connection removable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass approx. 100 g
Dimensions 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Data for application in connection with hazardous areas:
EC-Type Examination Certificate BVS 11 ATEX E 116 X
  Group, category, type of protection, temperature class Ex-Hexagon II 3(1) G Ex nA [ia Ga] IIC T4 Gc
Ex-Hexagon I (M1) [Ex ia Ma] I
Ex-Hexagon II (1) D [Ex ia Da] IIIC
Input  
  Voltage 27 V
  Current 87 mA
  Power 575 mW (linear characteristic)
Output  
  Voltage 27 V
  Current 87 mA
  Power 575 mW (linear characteristic)
Galvanic isolation  
  Rated voltage 250 V field circuits to control and supply circuits
  Input/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
  Output/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2009
EN 60079-11:2007
EN 60079-15:2010
EN 60079-26:2007
EN 61241-11:2006
EN 50303:2000
International approvals:
ATEX approval BVS 11 ATEX E 116X
UL approval E106378
IECEx approval BVS 11.0068X
  Approved for Ex nAc [ia] IIC T4
[Ex ia] IIIC
[Ex ia] I
EAC approval Russia: RU C-IT.MIII06.B.00129
Marine approval  
  Lloyd Register 15/20021
  American Bureau of Shipping T1450280/UN
  Bureau Veritas Marine 22449/B0 BV