通用输入输出模块 LB7004A

来源:未知    日期:2017/02/20    浏览量:


● 4-channel
● Analog input, digital input,
● analog output, digital output
● Installation in Zone 2 or safe area
● Supply circuit 21.5 V (4 mA)
● HART communication via field bus or service bus
● Simulation mode for service operations (forcing)
● Line fault detection (LFD): one LED per channel
● Permanently self-monitoring
● Module can be exchanged under voltage


Supply:
Connection backplane bus
Rated voltage 12 V DC , only in connection with the power supplies LB9***
Power dissipation 1.5 W
Power consumption 3 W
Internal bus:
Connection backplane bus
Interface manufacturer-specific bus to standard com unit
Input:
Number of channels 4
Connection Analog input (HART) : terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Digital Input : terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Output:
Number of channels 4
Connection Analog output (HART) : terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Digital Output : terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Watchdog output off 0.5 s after serious fault
Analog input:
Suitable field devices transmitters for pressure, differential pressure, level, flow, temperature, etc.
Transmitter supply voltage 21.5 V at 4 mA
Line fault detection can be switched on/off for each channel via configuration tool , configurable via configuration tool
  Short-circuit Ex works settings: > 21 mA configurable between 0 ... 26 mA
  Open-circuit Ex works settings: < 3.6 mA configurable between 0 ... 26 mA
Analog output:
Suitable field devices proportional valves , I/P converters , local indicators
Line fault detection can be switched on/off for each channel via configuration tool , configurable via configuration tool
  Short-circuit Ex works settings: < 50 Ω configurable between 0 ... 26 mA
  Open-circuit deviation of preset output value > 0.5 mA
Load 750 Ω max.
Digital input:
Suitable field devices mech. contacts or optocouplers
Switching point: OFF < 1.2 mA
Switching point: ON > 2.1 mA
Line fault detection can be switched on/off for each channel via configuration tool
  Connection mechanical switch with additional resistors (see connection diagram)
  Short-circuit > 7 mA
  Open-circuit < 0.1 mA
Digital output:
Suitable field devices solenoid valves, acoustic alarms and LED indicators (line fault detection can be deactivated)
Drive capability 12 V / 25 mA
Open loop voltage min. 22.7 V
Current limit 26 mA
Line fault detection can be switched on/off for each channel via configuration tool
  Test current 0.4 mA
  Short-circuit < 50 Ω
  Open-circuit < 0.2 mA
Internal resistance 385 Ω
Transfer characteristics:
Deviation 0.1 % of the signal range at 20 °C (68 °F)
Refresh time approx. 100 ms (4 channels)
Indicators/settings:
LED indicator Power LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1)
Configuration LED (AI, AO, DI, DO) white: selected channel mode
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2006
Conformity:
Electromagnetic compatibility NE 21:2007
Degree of protection IEC 60529:2000
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Shock resistance shock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistance frequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications:
Degree of protection IP20 (module) , mounted on backplane
Connection removable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass approx. 100 g
Dimensions 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Data for application in connection with hazardous areas:
Input  
  Voltage 27 V
  Current 87 mA
  Power 575 mW (linear characteristic)
Output  
  Voltage 27 V
  Current 87 mA
  Power 575 mW (linear characteristic)
Statement of conformity BVS 12 ATEX E 115 X
  Group, category, type of protection, temperature class Ex-Hexagon II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation  
  Rated voltage 250 V field circuits to control and supply circuits
  Input/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
  Output/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2009
EN 60079-11:2007
EN 60079-15:2010
International approvals:
ATEX approval BVS 12 ATEX E 115 X
IECEx approval BVS 11.0068X
  Approved for International: Ex nA [ia Ga] IIC T4 Gc
EAC approval Russia: RU C-IT.MIII06.B.00129
Marine approval  
  Lloyd Register 15/20021
  American Bureau of Shipping T1450280/UN
  Bureau Veritas Marine 22449/B0 BV