以太网和低速现场总线接口 KT-MB-GT2AD.FF

来源:未知    日期:2017/03/01    浏览量:


● System integration kit for Advanced Diagnostics
● PCS integration via Diagnostic Manager or device DTM
● Simple automatic setup of Advanced Diagnostics
● Common alarm handling
● For FOUNDATION Fieldbus and PROFIBUS PA
● Installation in Zone 2


General specifications:
Design / Mounting Motherboard based
Supply:
Rated voltage 19.2 ... 35 V DC SELV/PELV
Rated current 120 ... 70 mA
Power dissipation max. 2.5 W
Fieldbus interface:
Fieldbus type FOUNDATION Fieldbus
Physical layer profile profile type 114
ITK version 6
Implementation resource block1x RS
function block4x MDI, 1x MDO, 1x MAI, 1x DI
transducer block16x ADM TB, 1x IO TB
Firmware update Ethernet
Polarity polarity-sensitive
Rated voltage 9 ... 35 V SELV/PELV
Rated current 0 mA
Ethernet Interface:
Port 100 BASE-TX
Protocol TCP/IP and UDP/IP
Services ICMP , DHCP , AutoIP , HTTP
Connection type RJ-45 socket, 8-pin
Transfer rate 100 MBit/s
Diagnostic Bus:
Number of Diagnostic Bus Channels 2
Number of Diagnostic Modules/Channel 31 Using Ethernet Interface , 8 Using Fieldbus Interface
Termination integrated
Cable length/Channel 30 m
Indicators/operating means:
LED ERR red: Hardware fault
LED PWR green: Power on
LINK/ACT yellow
CH1, CH2 yellow: diagnostic bus activity
Outputs:
Output I alarm output diagnostic bus channel 1 , volt-free contact , NC contact
  Voltage 50 V DC
  Current max. 1 A
Output II alarm output diagnostic bus channel 2 , volt-free contact , NC contact
  Voltage 50 V DC
  Current max. 1 A
Output III common alarm , volt-free contact , NC contact
  Voltage 50 V DC
  Current max. 1 A
Galvanic isolation:
All circuits/FE functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output I, II/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Ethernet/Supply functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Ethernet/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Fieldbus/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Diagnostic Bus/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013
Low voltage  
  Directive 73/23/EEC EN 61010
Standard conformity:
Galvanic isolation IEC 62103
Electromagnetic compatibility NE 21
Degree of protection IEC 60529
Fieldbus standard IEC 61158-2
Climatic conditions DIN IEC 721
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ethernet IEEE 802.3
Ambient conditions:
Ambient temperature -40 ... 60 °C (-40 ... 140 °F) hazardous area
-40 ... 70 °C (-40 ... 158 °F) safe area horizontal DIN rail mounting
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity < 95 % non-condensing
Shock resistance 15 g 11 ms
Vibration resistance 1 g , 10 ... 150 Hz
Pollution degree max. 2, according to IEC 60664
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications:
Housing material Polycarbonate
Housing width see dimensions
Housing height see dimensions
Housing depth see dimensions
Degree of protection IP20
Mass 470 g
Mounting DIN rail mounting
Data for application in connection with hazardous areas:
Certificate TÜV 14 ATEX 115980 X
  Marking Ex-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals:
IECEx approval IECEx TUN 14.0003X
  Approved for Ex nA IIC T4 Gc