来源:未知 日期:2017/07/18 浏览量:次
一般特性: | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components |
Temperature Multi-Input Device RD0-TI-Ex8.PA.ST For technical data on installed electronic component see data sheet. |
|
符合: | ||
Degree of protection | EN 60529 | |
周围环境: | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity |
< 75 % (annual mean) < 95 % (30 d/year), no moisture condensation |
|
机械特性: | ||
Degree of protection | IP66 | |
Dimensions |
(W x H x D) 271 x 271 x 136 mm (1 x RD0-TI-Ex8.FF.ST) |
|
Mounting | thru-holes Ø6.5 mm | |
与危险区域有关的应用数据: | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Certificate | PF 16 CERT 3134 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Marking |
II 3G Ex ic IIC T4 Gc II 3G Ex nA IIC T4 Gc II 3D Ex tc IIIC T135°C Dc |
|
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2014 | |
国际认证: | ||
IECEx approval |
IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request |
|
INMETRO | TÜV 13.1143 |