联系方式
联系人:王经理
 
电 话:021-39520660
 
手  机:15821591180
 
传 真:021-69001586
 
Q    Q:1257746205
 
Email:debon_gk@163.com
 

频率信号转换安全栅 KFD2-UFC-Ex1.D

来源:未知    日期:2017/03/01    浏览量:


● 1-channel isolated barrier
● 24 V DC supply (Power Rail)
● Input for NAMUR sensors or dry contacts
● Input frequency 1 mHz ... 5 kHz
● Current output 0/4 mA ... 20 mA
● Relay and transistor output
● Start-up override
● Line fault detection (LFD)
● Up to SIL 2 acc. to IEC 61508/IEC 61511


产品阐述:
24 V DC
General specifications:
Signal type Digital Input
Supply:
Connection terminals 23+, 24- or power feed module/Power Rail
Rated voltage 20 ... 30 V DC
Rated current approx. 100 mA
Power dissipation/power consumption ≤ 2 W / 2.2 W
Input:
Connection Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
Input I sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
  Pulse duration > 50 µs
  Input frequency 0.001 ... 5000 Hz
  Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
  Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
  Open circuit voltage/short-circuit current 18 V / 5 mA
Output:
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
Output I, II signal, relay
  Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
  Mechanical life 5 x 107 switching cycles
  Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output III electronic output, passive
  Contact loading 40 V DC
  Signal level 1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA)
Output IV analog
  Current range 0 ... 20 mA or 4 ... 20 mA
  Open loop voltage max. 24 V DC
  Load max. 650 Ω
  Fault signal downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Collective error message Power Rail
Transfer characteristics:
Output IV  
  Resolution < 10 µA
  Accuracy < 20 µA
  Influence of ambient temperature 0.005 %/K (50 ppm)
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage  
  Directive 2014/35/EU EN 61010-1:2010
Conformity:
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications:
Degree of protection IP20
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas:
EC-Type Examination Certificate TÜV 99 ATEX 1471
  Group, category, type of protection Ex-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Statement of conformity TÜV 02 ATEX 1885 X
  Group, category, type of protection, temperature class Ex-Hexagon II 3G Ex nA nC IIC T4 Gc
Output I, II  
  Contact loading 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals:
FM approval  
  Control drawing 16-538FM-12
UL approval E223772
IECEx approval IECEx TUN 04.0007
  Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I