开关量输入安全栅 KCD2-SR-Ex1.LB

来源:未知    日期:2017/02/15    浏览量:


● 1-channel isolated barrier
● 24 V DC supply (Power Rail)
● Dry contact or NAMUR inputs
● Usable as signal splitter (1 input and 2 outputs)
● Relay contact output
● Fault relay contact output
● Line fault detection (LFD)
● Housing width 12.5 mm
● Up to SIL 2 acc. to IEC 61508


产品阐述:
24 V DC
General specifications:
Signal type Digital Input
Supply:
Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30 V DC
Ripple ≤ 10 %
Rated current ≤ 30 mA
Power dissipation ≤ 500 mW
Power consumption ≤ 500 mW
Input:
Connection terminals 1+, 2-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio min. 20 ms / min. 20 ms
Output:
Connection output I: terminals 5, 6 ; output II: terminals 7, 8
Output I signal ; relay
Output II signal or error message ; relay
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load
Minimum switch current 2 mA / 24 V DC
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Mechanical life 107 switching cycles
Transfer characteristics:
Switching frequency ≤ 10 Hz
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage  
  Directive 2014/35/EU EN 61010-1:2010
Conformity:
Electromagnetic compatibility NE 21
Degree of protection IEC 60529:2001
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications:
Degree of protection IP20
Mass approx. 100 g
Dimensions 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas:
EC-Type Examination Certificate BASEEFA 06 ATEX 0092
  Group, category, type of protection Ex-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC , Ex-Hexagon I (M1) [Ex ia Ma] I
Statement of conformity PF 06 CERT 0972 X
  Group, category, type of protection, temperature class Ex-Hexagon II 3G Ex nA nC IIC T4 Gc
Output I, II  
  Contact loading 50 V AC/2 A/cos φ > 0.7; 30 V DC/2 A resistive load
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals:
FM approval  
  Control drawing 116-0419 (cFMus)
UL approval  
  Control drawing 116-0420 (cULus)
IECEx approval IECEx BAS 06.0025
  Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I