联系方式
联系人:王经理
 
电 话:021-39520660
 
手  机:15821591180
 
传 真:021-69001586
 
Q    Q:1257746205
 
Email:debon_gk@163.com
 

开关量输入安全栅 HiC2821

来源:未知    日期:2017/03/09    浏览量:


H 系列可将多个隔离栅安装在端子板上,连接危险区现场设备和控制系统。与单一接口模块相比,端子板极大地简化接线,节省了成本。   端子板配有坚固的塑料机壳,便于在机柜内快速稳固的安装。在端子板上有多个安装卡槽,工程人员不必使用工具即可将隔离栅安装在端子板上。隔离栅模块支持热插拔。可选的故障监测端子板使得操作及维护更加快捷。

配有电缆连接头的预置电缆可以简化设计和文档管理。这些电缆代替了端子板与控制器I/O卡件(DCS,ESD)之间繁杂的点对点接线.

多种接口模块可以实现本质安全现场信号与自动化系统之间的电气隔离。

产品特点:● 1-channel isolated barrier
               ● 24 V DC supply (bus powered)
               ● Dry contact or NAMUR inputs
               ● Usable as signal splitter (1 input and 2 outputs)
               ● Relay contact output
               ● Fault relay contact output
               ● Line fault detection (LFD)
               ● Up to SIL 2 acc. to IEC 61508


一般规格:
Signal type Digital Input
Supply:
Connection SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage 19 ... 30 V DC via Termination Board
Ripple ≤ 10 %
Rated current ≤ 30 mA
Power dissipation ≤ 500 mW
Power consumption ≤ 500 mW
输入:
Connection SL2: 5a(+), 5b(-)
Rated values acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit current approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio min. 20 ms / min. 20 ms
输出:
Connection SL1: 8a, 7a; 10a, 9a
Output I signal ; relay
Output II signal or error message ; relay
Contact loading 50 V DC / 0.5 A
Minimum switch current 2 mA / 24 V DC
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Mechanical life 107 switching cycles
Error message output:
Connection SL1: 6b
Output type open collector transistor (internal fault bus)
Transfer characteristics:
Switching frequency ≤ 10 Hz
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity:
Galvanic isolation EN 50178:1997
Electromagnetic compatibility NE 21:2006
For further information see system description.
Degree of protection IEC 60529:2001
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications:
Degree of protection IP20
Mass approx. 100 g
Dimensions 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mounting on Termination Board
Data for application in connection with hazardous areas:
EC-Type Examination Certificate BASEEFA 06 ATEX 0093 X
  Group, category, type of protection Ex-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Statement of conformity PF 08 CERT 1047 X
  Group, category, type of protection, temperature class Ex-Hexagon II 3G Ex nA nC IIC T4 Gc
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals:
FM approval  
  Control drawing 16-534FM-12 (cFMus)
IECEx approval IECEx BAS 06.0026X
  Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

隔离式安全栅在安装中时的注意事项:
1.隔离式安全栅应安装在安全场所,并环境条件能满足本手册《通用技术指标》中的“使用条件”的要求。
2.隔离式安全栅本安端(蓝色标记)和非本安端电路的接线导线在汇线槽中应分开铺设,各自采用独立的保护套管。本安侧的配线套管内不允许有其它电源线,包括其本安电路使用的电源线。
3.通往危险场所的导线应选用有蓝色标记的本安导线,导线线的软铜面积必须大于0.5mm2,绝缘强度应大于500V。
4.在对隔离式安全栅进行通电调试前,必须注意隔离式安全栅的型号、接线方法、线路极性等,是否符合设计及产品要求中的规定,否则可能对人身及设备造成伤害。
5.严禁用兆欧表测试隔离安全栅端子之间的绝缘强度。如要检查系统的绝缘强度,应先断开全部的接线,否则可能引起安全栅内部快速熔断器熔断。
6.在现场对安全栅进行编程前,必须先将所有接线断开再接入编程器,然后通电编程,否则可能引起不良后果。
7.与隔离式安全栅相连的现场仪表,均应通过经国家认定的防爆检验部门的防爆试验、并取得防爆合格证的仪表。
8.在设计、安装、使用、维护隔离式安全栅时,应同时遵守本产品手册中的说明及《GB3836.15-2000爆炸性气体环境用电气设备 第十五部分:危险场所电气安装(煤矿除外)》、《GB50058-1992 爆炸和火灾危险环境电力设置设计规范》。