终端板 FC-GPCD-SDI16-PF

来源:未知    日期:2017/02/17    浏览量:


● System board for Honeywell Safety Manager
● For 16-channel DI card SDI-1624
● For 8 modules
● Recommended module: HiC2822 (DI)
● 24 V DC supply
● Hazardous area: pluggable screw terminals, blue
● Safe area: SiC plug, 20-pin


Supply:
Connection terminal block TB3 (1-, 2+; 3-, 4+)
Rated voltage 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple ≤ 10 %
Fusing 2 A
Power dissipation ≤ 500 mW , without modules
Reverse polarity protection yes
Electrical specifications:
volt-free fault indication output max. 30 V AC/40 V DC, 2 A
Redundancy:
Supply Redundancy available. The supply for the modules is decoupled, monitored and fused.
Indicators/settings:
Display elements LEDs PWR ON (power supply)
- LED power supply I, green LED
- LED power supply II, green LED
LED Fault (fault indication), green LED
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity:
Electromagnetic compatibility NE 21:2012
For further information see system description.
Degree of protection IEC 60529:2001
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications:
Degree of protection IP20
Connection hazardous area connection (field side): pluggable screw terminals, blue
safe area connection (control side): SiC plug, 20-pin
Core cross-section 0.2 ... 2.5 mm2 (24 ... 12 AWG)
Material housing: polycarbonate, 30 % glass fiber reinforced
Mass approx. 450 g
Dimensions 159 x 155 x 153 mm (L x W x H) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas:
EC-Type Examination Certificate CESI 06 ATEX 022
  Group, category, type of protection Ex-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Safe area  
  Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Galvanic isolation  
  Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000
International approvals:
UL approval  
  Control drawing 116-0327
IECEx approval IECEx CES 06.0003
  Approved for [Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I