来源:未知 日期:2017/02/16 浏览量:次
General specifications: | ||
---|---|---|
Signal type | Analog input | |
Supply: | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 19 ... 30 V DC | |
Rated current | approx. 120 mA at 24 V DC | |
Power dissipation | 2.3 W | |
Power consumption | 2.9 W | |
HART signal channels (intrinsically safe): | ||
Conformity | HART field device input (revision 5 to 7) | |
Input: | ||
Connection | terminals 1, 2, 3, 4, 5, 6 | |
Input signal | HART communication, transmitter supply | |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
Input resistance | 250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
Available voltage | ≥ 15.5 V at 20 mA, short-circuit protected | |
Output: | ||
Connection | output I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21 | |
Output signal | analog | |
Current range | 4 ... 20 mA , source or sink mode | |
Load | max. 650 Ω , source mode | |
Voltage range | 5 ... 30 V , sink mode from external supply | |
Fault signal | downscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
Other outputs | HART communicator on terminals 22, 24 | |
Collective error message | Power Rail and LED red | |
Directive conformity: | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity: | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions: | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications: | ||
Degree of protection | IP20 | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas: | ||
EC-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
Group, category, type of protection | II (1)GD [Ex ia] IIC, [Ex iaD] | |
Statement of conformity | PF 07 CERT 1142 X | |
Group, category, type of protection, temperature class | II 3G Ex nA II T4 X | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |