HART回路转换器 KFD2-HLC-Ex1.D.4S

来源:未知    日期:2017/02/16    浏览量:


● 1-channel isolated barrier
● 24 V DC supply (Power Rail)
● HART field device input (revision 5 to 7) with transmitter power supply
● Usable as signal splitter (1 input and multiple outputs)
● 4 relay outputs (NO)
● 3 analog outputs 4 mA ... 20 mA
● Sink and source mode output
● Configurable by keypad


General specifications:
Signal type Analog input
Supply:
Connection Power Rail or terminals 23+, 24-
Rated voltage 19 ... 30 V
Rated current approx. 140 mA at 24 V DC
Power dissipation 2.7 W
Power consumption 3.3 W
HART signal channels (intrinsically safe):
Conformity HART field device input (revision 5 to 7)
Input:
Connection terminals 1, 2, 3, 4, 5, 6
Input signal HART communication, transmitter supply
Open circuit voltage/short-circuit current typ. 24 V / 28 mA
Input resistance 250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6)
Available voltage ≥ 15.5 V at 20 mA, short-circuit protected
Output:
Connection output I: terminals 10, 11, output II: terminals 11, 12, output III: terminals 16, 17, output IV: terminals 17, 18
output V: terminals 7, 8, 9, output VI: terminals 13, 14, 15, output VII: terminals 19, 20, 21
Output I, II, III, IV  
  Output signal relay and LED yellow
  Mechanical life 107 switching cycles
  Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output V, VI, VII  
  Output signal analog
  Current range 4 ... 20 mA , source or sink mode
  Load max. 650 Ω , source mode
  Voltage range 5 ... 30 V , sink mode from external supply
  Fault signal downscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value
Other outputs HART communicator on terminals 22, 24
Collective error message Power Rail and LED red
Transfer characteristics:
Relay programmable either for fault or trip value (with direction, hysteresis and delay)
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage  
  Directive 2014/35/EU EN 61010-1:2010
Conformity:
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications:
Degree of protection IP20
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas:
EC-Type Examination Certificate BASEEFA 07 ATEX 0174
  Group, category, type of protection Ex-Hexagon II (1)GD [Ex ia] IIC, [Ex iaD]
Statement of conformity PF 07 CERT 1141 X
  Group, category, type of protection, temperature class Ex-Hexagon II 3G Ex nA nC II T4 X
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010

上一篇:没有了