联系方式
联系人:王经理
 
电 话:021-39520660
 
手  机:15821591180
 
传 真:021-69001586
 
Q    Q:1257746205
 
Email:debon_gk@163.com
 

Frequency Converter with Direction and Synchronization Monitor KFU8-UFT-2.D.FA

来源:未知    日期:2017/01/23    浏览量:


参数表节选:的技术参数 KFU8-UFT-2.D.FA

产品阐述
48 V AC ... 253 V AC/20 V DC ... 90 V DC
General specifications
Signal type Digital Input
Supply
Connection terminals 23, 24
Rated voltage 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Rated current approx. 130 mA
Power dissipation 2.2 W / 3.5 VA
Power consumption 2.5 W / 4 VA
Input
Connection input I: terminals 1+, 3-
input II: terminals 4+, 6-
input III: terminals 13+, 14- (control input 1)
input IV: terminals 15+, 14- (control input 2)
Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
  Open circuit voltage/short-circuit current 8.2 V / 10 mA
  Pulse duration min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
  Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
  Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Input III, IV  
  Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
  Open circuit voltage/short-circuit current 18 V / 5 mA
Output
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 19+, 20-
output IV: terminals 21+, 20-
output V: terminals 7-, 8+
Output I, II signal, relay
  Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
  Mechanical life 5 x 107 switching cycles
  Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output III and IV signal , electronic output, passive
  Contact loading 40 V DC
  Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
0-signal: blocked output (off-state current ≤ 10 µA)
Output V analog
  Current range 0 ... 20 mA or 4 ... 20 mA
  Open loop voltage max. 24 V DC
  Load max. 650 Ω
  Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Programming interface  
  Connection programming socket
  Interface RS 232
Transfer characteristics
Input I and II  
  Measurement range 0.001 ... 1000 Hz
  Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
  Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
  Measuring time frequency measurement: < 100 ms
  Influence of ambient temperature 0.003 %/K (30 ppm)
Directive conformity
Electromagnetic compatibility  
  Directive 2004/108/EC EN 61326-1:2006
Low voltage  
  Directive 2006/95/EC EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001