来源:未知 日期:2017/01/09 浏览量:次
产品阐述 | ||
---|---|---|
LED temperature display for thermocouples J/K/N, with 24 VDC supply voltage |
General specifications | ||
---|---|---|
Data storage | EEPROM | |
Programming | keypad-driven menu | |
Functional safety related parameters | ||
MTTFd | 1400 a | |
Mission Time (TM) | 10 a | |
Diagnostic Coverage (DC) | 0 % | |
Indicators/operating means | ||
Type | 5-digit 7-segment LED display, red | |
Display value | digit height 8 mm | |
Display interval | -999.9 ... 1999.9 | |
Decimal point | 0 to max 1 fractional digit | |
Temperature range |
acc. DIN IEC 584: J (Fe-Cu-Ni): -210 ... 1200 °C (-346 ... 2192 °F) K (Ni-CrNi): -200 ... 1372 °C (-328 ... 2501.6 °F) N (NiCrSi-NiSi): -200 ... 1300 °C (-328 ... 2372 °F) |
|
Resolution | 0.1 °C (0.1 °F) bzw. 1 °C (1 °F) | |
Refresh cycle of the measured value output | 1 - 2 s-1 | |
Reset | manually or external | |
Electrical specifications | ||
Operating voltage | 10 ... 30 V DC galvanically isolated | |
Operating current | max. 40 mA | |
Input | ||
Suitable sensors | Thermocouple J, K, N, with sensor breakage monitoring | |
Signal voltage | Display latch, display hold for current measured value | |
High | 4 ... 30 V DC | |
Low | 0 ... 2 V DC | |
Counting frequency | 5 measurements per second | |
Linearity error | < 0.4 % at 20°C ambient temperature | |
Compensation (reference junction CJC) |
internal or external (programmable) Junction error: ±1.0 °C typ./±3.0 °C max. |
|
Compliance with standards and directives | ||
Directive conformity | ||
EMC Directive 2004/108/EC | EN 61000-6-2:2005 | |
Standard conformity | ||
Emitted interference | DIN EN 55011:2009, Class B | |
Ambient conditions | ||
Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Relative humidity | ≤ 85 % (noncondensing) | |
Temperature drift | 0.1 K/Kenvironment | |
Mechanical specifications | ||
Degree of protection | IP65 (front) | |
Mass | approx. 45 g | |
Dimensions | 48 mm x 24 mm x 68.3 mm |