来源:未知 日期:2017/09/12 浏览量:次
产品阐述: | ||
---|---|---|
KE1-Safety module for the control cabinet 2 safety-related inputs and 2 conventional electronic outputs |
一般特性: | ||
---|---|---|
Slave type | Safety-Slave | |
AS-Interface specification | V2.1 | |
Required master specification | ≥ V2.1 | |
UL File Number | E223772 | |
功能安全性参数: | ||
Safety Integrity Level (SIL) | SIL 3 | |
MTTFd | 200 a | |
指示灯/操作键: | ||
LED FAULT |
error display; LED red red: communication error or address is 0 red flashing: Output supply overload |
|
LED PWR | AS-Interface voltage; LED green | |
LED AUX | ext. auxiliary voltage UAUX ; LED green | |
LED IN | switching state (input); 2 LED yellow | |
LED OUT | Switching state (output); 2 LED yellow | |
电气特性: | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 70 mA | |
Protection class | III | |
Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) | |
输入: | ||
Number/Type |
2 safety-related inputs for mechanical contacts, cross-circuit monitored: 2 single-channel contacts: up to category 2 in accordance with EN 954-1 or 1, 2-channel contact: up to category 4 in accordance with EN 954-1 Cable length must not exceed 300 m per input. |
|
Supply | from AS-Interface | |
Voltage | 20 ... 30 V DC pulsed | |
Current loading capacity |
input current limited ≤ 15 mA, overload and short-circuit resistant |
|
输出: | ||
Number/Type | 2 conventional electronic outputs, PNP | |
Supply | from external auxiliary voltage UAUX | |
Current | 0.5 A per output | |
Voltage | ≥ (UAUX - 0.5 V) | |
与标准和规范体系的一致性: | ||
Directive conformity | ||
EMC Directive 2004/108/EC | EN 61326:2006, EN 50295:1999, EN 61496-1:2004 | |
Standard conformity | ||
Electromagnetic compatibility | EN 61000-6-2:2005, EN 61000-4-5:2005 1 kV asymmetric, criterion B, EN 61000-6-4:2007 | |
Emitted interference | EN 61000-6-4:2001 | |
Insulation coordination | EN 50178:1998 | |
Functional safety | EN ISO 13849-1:2006 up to PL e, IEC 61508:2009 up to SIL 3 | |
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 50295:1999, IEC 62026-2:2006 | |
Electrical safety | EN 50178:1998 , IEC 60204-1:2007 | |
编程指令: | ||
Profile | S-7.B | |
IO code | 7 | |
ID code | B | |
ID1 code | F | |
ID2 code | 0 | |
Data bits (function via AS-Interface) | 输入输出 | |
D0 | dyn. safety code 1 OUT 1 | |
D1 | dyn. safety code 1 OUT 2 | |
D2 | dyn. safety code 2 - | |
D3 | dyn. safety code 2 - | |
Parameter bits (programmable via AS-i) | 功能 | |
P0 |
Logic operation: P0 = 1 (default settings): The outputs are controlled via AS-Interface. P0 = 0: The outputs are controlled via AS-Interface or the inputs. The corresponding output is activated on opening the contacts of an input. |
|
P1 | not used | |
P2 | not used | |
P3 | not used | |
周围环境: | ||
Ambient temperature | -25 ... 50 °C (-13 ... 122 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Pollution degree | 2 | |
机械特性: | ||
Degree of protection | IP20 | |
Connection | removable terminals, terminal connection ≤ 2.5 mm2 | |
Material | ||
Housing | PA 66-FR | |
Mass | 80 g | |
Mounting | DIN mounting rail | |
Tightening torque of clamping screws | 0.5 Nm ... 0.6 Nm |