来源:未知 日期:2017/11/10 浏览量:次
产品阐述: | ||
---|---|---|
G4 module IP65 4 inputs (PNP) and 4 electronic outputs |
一般特性: | ||
---|---|---|
Slave type | Standard slave | |
AS-Interface specification | V3.0 | |
Required master specification | ≥ V2.0 | |
UL File Number | E223772 | |
功能安全性参数: | ||
MTTFd | 150 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
指示灯/操作键: | ||
LED PWR/FAULT |
dual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply or outputs |
|
LED AUX | ext. auxiliary voltage UAUX ; LED green | |
LED IN | switching state (input); 4 LED yellow | |
LED OUT | Switching state (output); 4 LED yellow | |
电气特性: | ||
Auxiliary voltage (output) | 24 V DC ± 15 % PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 30 mA (without sensors) / max. 230 mA | |
Protection class | III | |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) | |
输入: | ||
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC | |
Supply | from AS-Interface | |
Voltage | 21 ... 31 V | |
Current loading capacity |
≤ 200 mA (TB ≤ 40 °C), ≤ 160 mA (TB ≤ 60 °C), short-circuit protected |
|
Input current | ≤ 9 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 (Type 2) | |
0 (unattenuated) | ≤ 3 mA | |
1 (attenuated) | ≥ 5 mA | |
输出: | ||
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from external auxiliary voltage UAUX | |
Current | 1 A per output, 4 A total | |
Voltage | ≥ (UAUX - 0.5 V) | |
与标准和规范体系的一致性: | ||
Directive conformity | ||
EMC Directive 2004/108/EC | EN 61000-6-2:2005, EN 61000-6-4:2007, EN 50295:1999 | |
Standard conformity | ||
Noise immunity | EN 61000-6-2:2005, EN 50295:1999 | |
Emitted interference | EN 61000-6-4:2007 | |
Input | EN 61131-2:2007 | |
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 50295:1999, IEC 62026-2:2006 | |
编程指令: | ||
Profile | S-7.0 | |
IO code | 7 | |
ID code | 0 | |
ID1 code | F | |
ID2 code | E | |
Data bits (function via AS-Interface) | input output | |
D0 | IN1 OUT1 | |
D1 | IN2 OUT2 | |
D2 | IN3 OUT3 | |
D3 | IN4 OUT4 | |
Parameter bits (programmable via AS-i) | function | |
P0 |
communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
|
P1 | not used | |
P2 | not used | |
P3 | not used | |
周围环境: | ||
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Pollution degree | 3 | |
机械特性: | ||
Degree of protection | IP65 | |
Connection |
cable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs:M12 x 1.5 cable glands and cage tension spring terminals |
|
Material | ||
Housing | PA 6 GF30 | |
Mass | 350 g | |
Tightening torque, housing screws | 0.8 Nm | |
Mounting | DIN rail or screw mounting |