General specifications: |
AS-Interface specification |
V2.0 |
Diagnostics function |
integrated |
Functional safety related parameters: |
MTTFd |
140 a at 30 °C |
Indicators/operating means: |
Display |
LED display, 2 digits, for addressing and error messages |
LED BUS ACTIVE |
PROFIBUS master detected; LED green |
LED AS-i ACTIVE |
AS-Interface operation normal; LED green |
LED CONFIG ERR |
configuration error; LED red |
LED PWR |
voltage ON; LED green |
LED PRG ENABLE |
autom. programming; LED green |
LED PRG MODE |
projecting mode active; LED yellow |
LED U AS-i |
AS-Interface voltage; LED green |
Switch SET |
Selection and setting of a slave address |
Button MODE |
Mode selection/save configuration |
Electrical specifications: |
Insulation voltage |
≥ 500 V |
Rated operating voltage |
from AS-Interface |
Rated operating current |
≤ 180 mA from AS-Interface |
Interface: |
Interface type |
RS-485 |
Protocol |
PROFIBUS |
Transfer rate |
9.6; 19.2; 44.44; 93.95; 187.5; 500; 1500 kBit/s self-synchronizing |
Connection: |
PROFIBUS |
Cable gland M16 x 1.5 and cage spring terminals |
AS-Interface |
cable piercing technology |
Compliance with standards and directives: |
Standard conformity |
|
|
Degree of protection |
EN 60529 |
Ambient conditions: |
Ambient temperature |
0 ... 55 °C (32 ... 131 °F) |
Storage temperature |
-25 ... 85 °C (-13 ... 185 °F) |
Mechanical specifications: |
Degree of protection |
IP65 |
Material |
|
|
Housing |
PA 6 GF30 |
Mass |
420 g |
Construction type |
Plastic housing with cable gland |