Type X正压系统 6000 Control System

来源:未知    日期:2017/02/16    浏览量:


● Certified for Class I, Class II, Division I; Zone 1 / Zone 21 to nonhazardous
● Intrinsically safe electrical/pneumatic manifold assembly
● Intrinsically safe user interface for programming and monitoring the system
● Enclosure volume up to 450 ft3 (12.1 m3)
● Control Unit monitors system operation and controls enclosure power
● Universal mounting (brackets included)
● 316L stainless steel Type 4X enclosure


产品阐述:
Type X & Ex px purge and pressurization system
General specifications:
Operating mode manual, semi-automatic, or fully automatic - programmable
Number of volume exchanges 4 to 19
Hazardous environment gas, dust, gas and dust
Supply:
Rated voltage 90 ... 264 V AC, 48 ... 62 Hz / 0.2 A
20 ... 30 V DC
Electrical specifications:
Connection Terminal blocks
Input:
Input I Inputs 1, 2, 3, 4: contact input, 5 VDC @ 2 mA
  Input type Intrinsically Safe
Input II Temperature inputs
  Input type Intrinsically Safe
  Sensor type 6000-TEMP
Input III EPV-6000 Vent
  Input type Intrinsically Safe
Input IV User interface module
  Connection M8 connector, 4-pin
  Input type Intrinsically Safe
Output:
Output I AUX 1
  Output type Dry contacts, SPDT
  Inrush current 5 A
  Contact loading 2 A @ 240 VAC resistive load
2 A @ 24 VDC
Output II AUX 2
  Output type Dry contacts, SPDT
  Inrush current 5 A
  Contact loading 2 A @ 240 VAC resistive load
8 A @ 24 VDC
Output III ENC_1, ENC_2 (protected enclosure contacts)
  Output type Dry contacts (2) SPST, NO
  Contact loading 8 A @ 240 VAC / 120 VAC resistive load
8 A @ 24 VDC
Indicators/settings:
LED indicator Safe pressure: Blue - safe pressure is achieved
Enclosure power: Green - power on; Red - power off
Rapid exchange: Blue - purging is running
System bypass: Yellow - bypass is activated
Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - 6000 series system fault
Pneumatic parameters:
Protective gas supply instrument grade air or inert gas
Pressure requirement 20 ... 120 psig (1.4 ... 8.3 bar) (138 ... 827 kPa) regulated
Safe pressure Gas: 0.25" wc (6.4 mm wc) (0.625 mbar) (62 Pa)
Dust: 0.65" wc (16.5 mm wc) (1.6 mbar) (162 Pa)
Gas and Dust: 0.65" wc (16.5 mm wc) (1.6 mbar) ( 162 Pa)
Purge flow rate Maximum flow rate measurement for enclosure size (enclosure volume:flow rate):
< 20 ft³ (0.57m³): 5, 12 SCFM (56, 141, 340 l/min), or dynamic
20 ... 30 ft³ (0.57 ... 0.85 m³): 5, 12, 20 SCFM (56, 141, 340, 565 l/min), or dynamic
> 30 ft³ (0.85m³): 5, 12, 20, 30 SCFM (56, 141, 340, 565, 850 l/min), or dynamic
Purge flow and enclosure pressure rate With EPV-6000-xx-01, EPV-6000-xx-02
5 SCFM @ 1.5" wc, (141 l/min @ 3.7 mbar)
12 SCFM @ 2.0" wc, (340 l/min @ 5.0 mbar)
20 SCFM @ 2.7" wc, (565 l/min @ 6.7 mbar)
30 SCFM @ 4.1" wc, (850 l/min @ 10.2 mbar)

With EPV-6000-xx-03, EPV-6000-xx-04
5 SCFM @ 2.1" wc, (141 l/min @ 5.2 mbar
12 SCFM @ 2.6" wc, (340 l/min @ 6.5 mbar)
20 SCFM @ 4.1" wc, (565 l/min @ 10.2 mbar)
30 SCFM @ 5.3" wc, (850 l/min @ 13.2 mbar)

With EPV-6000-xx-05, EPV-6000-xx-06
5 SCFM @ 1.8" wc, (141 l/min @ 4.5 mbar)
12 SCFM @ 2.9" wc, (340 l/min @ 7.3 mbar)
20 SCFM @ 7.4" wc, (565 l/min @ 18.5 mbar)
Flow rate for leakage compensation Depends on enclosure seal.

With EPV-6000-xx-01, EPV-6000-xx-02
0.35 SCFM @ 0.25" wc (10.0 l/min @ 6.3 mbar)
1.0 SCFM @ 0.75" wc (28.0 l/min @ 1.9 mbar)

With EPV-6000-xx-03, EPV-6000-xx-04
0.22 SCFM @ 0.25" wc (6.2 l/min @ 6.3 mbar)
0.58 SCFM @ 0.75" wc (16.4 l/min @ 1.9 mbar)

With EPV-6000-xx-05, EPV-6000-xx-06
0.15 SCFM @ 0.25" wc (4.2 l/min @ 6.3 mbar)
0.35 SCFM @ 0.75" wc (10.0 l/min @ 1.9 mbar)
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -30 ... 80 °C (-22 ... 176 °F)
Relative humidity 5 ... 95 %, noncondensing
Vibration resistance 5 ... 100 Hz , 1 g, 12 m/s2, all axes
Impact resistance 30 g, 11 ms, all axes
Mechanical specifications:
Connection type Pneumatic :
Inlet fitting to manifold: 3/8" NPT (female)
Outlet fitting from manifold: 3/8" bulkhead fitting (provided)
Cable gland 4 - M16 x 1.5 cable gland
Degree of protection Type 4X , IP66
Material Enclosure: 316L (UNS S31603) stainless steel
Manifold valve: anodized 6082 aluminum
Fittings: 316L (UNS S31603) stainless steel
Mass -WH- 11.4 kg (25 lb)
-CK- 7.2 kg (16 lb)
Dimensions 183 x 367.5 x 152.5 mm (7.20 x 14.45 x 6.00 inch)
Data for application in connection with hazardous areas:
EU-Type Examination Certificate  
  Marking 6000 main control unit with housing
6000-xx-S2-UN-xx-xx:
ATEX UL/Demko 07 ATEX 0705753X
II 2 G Ex db [ib pxb] IIC T4 Gb (-20 °C ≤ Ta ≤ 60 °C)
II 2 D Ex ib tb [ib pxb] IIIC T60°C Db (-20 °C ≤ Ta ≤ 50 °C)

6000 main control unit kit version
6000-xx-S2-UN-CK-xx:
ATEX UL/Demko 07 ATEX 0705753X
II 2 G Ex db [ib pxb] IIC T4 Gb (-20 °C ≤ Ta ≤ 60 °C)
II 2 D Ex tb [ib pxb] IIIC T80°C Db (-20 °C ≤ Ta ≤ 60 °C)

User interface
6000-UIC-xx:
ATEX UL/Demko 07 ATEX 0705753X
II 2 G Ex ib [pxb] IIC T4 Gb
Directive conformity  
  Directive 94/9/EC IEC/EN 60079-0
IEC/EN 60079-1
IEC/EN 60079-2
IEC/EN 60079-7
IEC/EN 60079-11
IEC/EN 60079-31
International approvals:
UL approval 6000 Main control unit with housing
6000-xx-S2-UN-xx-xx:
cULus
Class I, Division 1, Groups A,B,C,D T4 (-20 °C ≤ Ta ≤ 60 °C)
Class II, Division 1, Groups E,F,G T4 (-20 °C ≤ Ta ≤ 50 °C)
Class I, Zone 1, Group IIC T4 (-20 °C ≤ Ta ≤ 60 °C)
Class II, Zone 21, Group IIIC T60 °C (-20 °C ≤ Ta ≤ 50 °C)
[Ex i] Associated Equipment
Ex db [ib pxb] IIC T4 (-20 °C ≤ Ta ≤ 60 °C)
Ex db tb [ib pxb] IIIC T4 (-20 °C ≤ Ta ≤ 50 °C)

6000 Main control unit kit version
6000-xx-S2-UN-CK-xx:
cULus
Class I, Division 1, Groups A,B,C,D T4 (-20 °C ≤ Ta ≤ 60 °C)
Class II, Division 1, Groups E,F,G T4 (-20 °C ≤ Ta ≤ 60 °C)
Class I, Zone 1, Group IIC T4
Class II, Zone 21, Group IIIC T60 °C
[Ex i] Associated Equipment
Ex db [ib pxb] IIC T4 X (-20 °C ≤ Ta ≤ 60 °C)
Ex db [ib pxb] IIIC T4 X (-20 °C ≤ Ta ≤ 60 °C)

User interface
6000-UIC-xx:
cULus
(-20 °C ≤ Ta ≤ 60 °C)
Class I, Division 1, Groups A,B,C,D T4
Class I, Zone 1, Group IIC T4
Ex i Intrinsically safe
IECEx approval 6000 Main Control unit with housing
6000-xx-S2-UN-xx-xx:
IECEx UL 08.0003X
Ex db [ib pxb] IIC T4 Gb (-20 °C ≤ Ta ≤ 60 °C)
Ex db tb [ib pxb] IIIC T60 °C Db (-20 °C ≤ Ta ≤ 50 °C)

6000 Main control unit kit version
6000-xx-S2-UN-CK-xx:
IECEx UL 08.0003X
Ex db [ib pxb] IIC T4 Gb (-20 °C ≤ Ta ≤ 60 °C)
Ex db [ib pxb] IIIC T80 °C Db (-20 °C ≤ Ta ≤ 60 °C)

User interface
6000-UIC-xx:
IECEx UL 08.0003X
Ex ib [pxb] IIC T4 Gb