来源:未知 日期:2017/04/07 浏览量:次
Supply: | ||
---|---|---|
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power consumption | 0.6 W | |
内部总线: | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
输入: | ||
Number of channels | 4 | |
Suitable sensors | 2-, 3- , 4-wire connection, thermocouple , slide wire sensors | |
Connection |
channel I: resistance/potentiometer input 1 ... 4 channel II: resistance/potentiometer input 5 ... 8 channel III: resistance/potentiometer input 9 ... 12 channel IV: resistance/potentiometer input 13 ... 16 |
|
Lead resistance | max. 50 Ω per strand | |
Measurement range |
Pt100 (18-390 Ω) (500 Ω incl. line resistance) Pt200 (37-780 Ω) Pt500 (92-1952 Ω) Pt1000 (185-3905 Ω) Ni100 (69-270 Ω) Ni500 (345-1350 Ω) Ni1000 (690-2700 Ω) |
|
Slide-wire sensor | 0 ... 10000 Ω | |
Measuring current | 200 µA | |
Line fault detection | can be switched on/off for each channel via configuration tool | |
Short-circuit | < 10 Ω | |
Open-circuit | > 1 kΩ | |
Busy after download | 5 ... 15 s | |
指标/设置: | ||
LED indicator |
LED green: supply LED red: line fault, collective alarm , flashing: communication error |
|
指令符合: | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1 | |
符合: | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
周围环境: | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100 | |
Vibration resistance | frequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
机械特性: | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection |
removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
|
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
与危险区域有关的应用参数: | ||
EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
Marking |
II 2(1) G Ex d [ia Ga] IIC Gb II (1) D [Ex ia Da] IIIC |
|
Input | ||
Voltage | 7.14 V | |
Current | 70 mA | |
Power | 123 mW (linear characteristic) | |
Galvanic isolation | ||
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU |
EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 |
|
国际认证: | ||
ATEX approval | PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
DNV GL Marine | TAA0000034 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |