联系方式
联系人:王经理
 
电 话:021-39520660
 
手  机:15821591180
 
传 真:021-69001586
 
Q    Q:1257746205
 
Email:debon_gk@163.com
 

数字量输入模块 FB1202B

来源:未知    日期:2017/03/01    浏览量:


● 3-channel
● Inputs Ex ia
● Dry contact or NAMUR inputs
● Installation in suitable enclosures in Zone 1 or Zone 21
● Positive or negative logic selectable
● Simulation mode for service operations (forcing)
● Line fault detection (LFD)
● Permanently self-monitoring
● Module can be exchanged under voltage (hot swap)


Supply:
Connection backplane bus
Rated voltage 12 V DC , only in connection with the power supplies FB92**
Power consumption 0.5 W
Internal bus:
Connection backplane bus
Interface manufacturer-specific bus to standard com unit
Input:
Number of channels 3
Suitable sensors mechanical contacts, NAMUR proximity switches, 2-wire initiators
Connection channel I: 1+, 4-; channel II: 2+, 5-; channel III: 3+, 6-
Rated values acc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis 1.2 ... 2.1 mA / ± 0.2 mA
Voltage 8.2 V
Line fault detection can be switched on/off for each channel via configuration tool
  Connection mechanical switch with additional resistors (see connection diagram) , proximity switches without additional wiring
  Short-circuit < 360 Ω
  Open-circuit < 0.35 mA
Indicators/settings:
LED indicator LED green: supply
LED red: line fault, channel 1
LED yellow: status channel 1
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1
Conformity:
Electromagnetic compatibility NE 21
Degree of protection IEC 60529
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Relative humidity 95 % non-condensing
Shock resistance shock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistance frequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications:
Degree of protection IP20 (module) , a separate housing is required acc. to the system description
Connection removable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass approx. 330 g
Dimensions 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas:
EC-Type Examination Certificate PTB 97 ATEX 1074 U
  Group, category, type of protection Ex-Hexagon II 2(1) G Ex d [ia Ga] IIC Gb
Ex-Hexagon II (1) D [Ex ia Da] IIIC
Input  
  Voltage 10.5 V
  Current 35 mA
  Power 92 mW (linear characteristic)
Galvanic isolation  
  Input/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2007
EN 60079-26:2007
EN 61241-11:2006
International approvals:
ATEX approval PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U
EAC approval Russia: RU C-IT.MIII06.B.00129
Marine approval  
  Lloyd Register 15/20021
  DNV GL Marine TAA0000034
  American Bureau of Shipping T1450280/UN
  Bureau Veritas Marine 22449/B0 BV