模拟量输入模块 FB3205B2

来源:未知    日期:2017/02/15    浏览量:


● 4-channel
● Inputs Ex ia
● Power supply for 2-wire transmitters with 4 mA ... 20 mA
● Supply circuit 15 V (20 mA)
● Input from active signals of 4-wire transmitters
● Installation in suitable enclosures in Zone 1 or Zone 21
● HART communication via field bus or service bus
● Simulation mode for service operations (forcing)
● Line fault detection (LFD)
● Permanently self-monitoring
● Module can be exchanged under voltage (hot swap)


Supply:
Connection backplane bus
Rated voltage 12 V DC , only in connection with the power supplies FB92**
Power dissipation 1.5 W
Power consumption 3 W
Internal bus:
Connection backplane bus
Interface manufacturer-specific bus to standard com unit
Input:
Number of channels 4
Suitable field devices transmitters for pressure, differential pressure, level, flow, temperature, etc.
Connection 2-wire transmitter (HART):
supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14-
3-wire transmitter:
supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16-
measuring circuit: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-
4-wire transmitter (separately powered):
measuring circuit: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-
Input resistance 15 Ω (channel I: 3, 4; channel II: 7, 8; channel III: 11, 12; channel IV: 15, 16)
Line fault detection can be switched on/off for each channel via configuration tool , configurable via configuration tool
  Short-circuit Ex works settings: > 22 mA configurable between 0 ... 26 mA
  Open-circuit Ex works settings: < 1 mA configurable between 0 ... 26 mA
Transmitter supply voltage 15 V at 20 mA
Transfer characteristics:
Deviation  
  After calibration 0.1 % of the signal range at 20 °C (68 °F)
Resolution 12 Bit (0 ... 26 mA)
Refresh time 100 ms
Indicators/settings:
LED indicator Power LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-4) red: line fault (lead breakage or short circuit)
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2006
Conformity:
Electromagnetic compatibility NE 21:2007
Degree of protection IEC 60529:2000
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Relative humidity 95 % non-condensing
Shock resistance shock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistance frequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications:
Degree of protection IP20 (module) , a separate housing is required acc. to the system description
Connection removable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass approx. 750 g
Dimensions 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas:
EC-Type Examination Certificate BVS 12 ATEX E 101 X
  Group, category, type of protection, temperature class Ex-Hexagon II 2(1) G Ex d [ia Ga] IIC T4 Gb
Ex-Hexagon II (1) D [Ex ia Da] IIIC
Supply  
  Voltage 27 V
  Current 90 mA
  Power 588 mW (linear characteristic)
Input  
  Voltage 0.7 V
  Current 2.78 mA
  Power 2 mW (trapezoid characteristic curve)
  Internal capacitance 242 nF
  Internal inductance 0 mH
Galvanic isolation  
  Input/power supply, internal bus safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2012
EN 60079-26:2007
International approvals:
ATEX approval BVS 12 ATEX E 101 X
INMETRO Brazil: TÜV 14.1597X
Marine approval  
  Bureau Veritas Marine 22449/B0 BV