来源:未知 日期:2017/07/20 浏览量:次
一般特性: | ||
---|---|---|
Measuring method | A piezoelectric drive excites the vibrating rod of the device to its resonance frequency. If medium covers the vibrating rod, the rod's vibrating amplitude changes (the vibration is damped). The electronics of the device compare the actual amplitude with a target value and indicates whether the vibrating rod is vibrating freely or whether it is covered by medium. | |
Equipment architecture |
The measuring system consists of: - the device with electronic insert - a supply point - the connected control systems, switching units, signalling systems (e. g. lamps, horns, PCS, PLC, etc.) |
|
Construction type | device with pipe extension | |
Operating mode |
MAX = maximum safety: The device switches if the probe is covered or if the supply voltage is disconnected in a safety-oriented manner (signal on alarm). example application: overspill protection MIN = minimum safety: The device switches if the probe is uncovered or if the supply voltage is disconnected in a safetyoriented manner (signal on alarm). example application: dry-running protection |
|
Supply: | ||
Rated voltage |
electronic insert FEM22 (E5): 10 ... 45 V DC electronic insert FEM24 (WA): 19 ... 253 V AC, 50/60 Hz or 19 ... 55 V DC |
|
Ripple | electronic insert FEM22 (E5): max. 5 V, 0 ... 400 Hz | |
Current consumption | electronic insert FEM22 (E5): max. 18 mA | |
Reverse polarity protection | separation voltage 2.2 kV | |
电气特性: | ||
Surge protection | electronic insert FEM22 (E5) : overvoltage category III | |
输入: | ||
Input signal |
probe covered - small amplitude probe not covered - large amplitude |
|
Measured variable | level (according to the mounting location and the overall length) | |
Measurement range |
The measuring range depends on the mounting location of the device and the length of the pipe extension selected. The pipe extension is available in the following lengths: 500 mm, 1000 mm, 1500 mm, 20 inch, 40 inch, 60 inch |
|
输出: | ||
Output signal | digital | |
电流隔离: | ||
Input/Other circuits | electronic insert FEM24 (WA) | |
指令符合: | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | electronic insert FEM24 (WA) : EN 61010-1:2010 | |
符合: | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529:2001 | |
Vibration resistance | EN 60068-2-27 | |
Climate class | EN 60068, part 2-38, fig. 2a | |
测量精度: | ||
Measuring frequency | 700 ... 800 Hz | |
Switching time | when covering the sensor approx. 0.5 s, when uncovering the sensor approx. 1.0 s | |
操作条件: | ||
Installation conditions | ||
Installation position | see section mounting position | |
Process conditions | ||
Process temperature | -40 ... 150 °C (-40 ... 302 °F) | |
Medium pressure limits |
-1 ... 25 bar max. working pressure 25 bar, burst pressure 100 bar |
|
Thermal shock resistance | max. 120 K | |
State of aggregation | solids | |
Solid contents | ≤ ∅25 mm | |
Bulk density | ≥ 200 g/l, not fluidised | |
周围环境: | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
机械特性: | ||
Degree of protection | IP66/IP67, NEMA 4X | |
Connection |
gland M20 thread G1/2, NPT1/2 |
|
Material |
F16 housing: PTB-FR, cover with transparent glass made of PA12, EPDM cover seal F18 housing: aluminum EN-AC-AlSi10Mg, plastic coated cover seal: EPDM process connections, sensor: stainless steel 1.4435/316L |
|
Mass |
device with F16 housing, electronic insert FEM24 (WA) and R1 thread: - 500 mm (20 inch) = approx. 1.3 kg - 1000 mm (40 inch) = approx. 2.0 kg - 1500 mm (60 inch) = approx. 2.6 kg |
|
Dimensions |
max. ∅85 mm (3.3 inch), length 160 mm (6.3 inch) + L L = 500 mm, 1000 mm, 1500 mm, 20 inch, 40 inch, 60 inch |
|
Process connection |
thread R1, R1-1/2 acc. to DIN 2999 thread 1-1/4 - 11-1/2 NPT, 1-1/2 - 11-1/2 NPT acc. to ANSI B 1.20.1 |
|
与危险区域有关的应用数据: | ||
EC-Type Examination Certificate | KEMA 06 ATEX 0055 | |
Group, category, type of protection | II 1/3D Ex ta/tc IIIC T170°C Da/Dc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-31:2009 | |
国际认证: | ||
IECEx approval | IECEx DEK 11.0068 | |
Approved for | Ex ta/tc IIIC T170°C Da/Dc | |
附件: | ||
Optional accessories |
LVL-Z200 sliding sleeve for pressurized containerLVL-Z201 sliding sleeve for pressurized container LVL-Z202 sliding sleeve for unpressurized container LVL-Z203 sliding sleeve for unpressurized container |
上一篇:振动限位开关 LVL-B1