来源:未知 日期:2017/03/21 浏览量:次
一般规格: | ||
---|---|---|
Measuring method | The tuning fork is brought to its resonance frequency by means of a piezoelectric drive. If the tuning fork is covered by liquid, this frequency changes. The electronics monitor the resonance frequency and indicate whether the tuning fork is freely vibrating or is covered by liquid. | |
Construction type |
compact device device with short tube |
|
Operating mode |
MAX = maximum safety: The device keeps the electronic switch closed as long as the liquid level is below the fork. example application: overspill protection MIN = minimum safety: The device keeps the electronic switch closed as long as the fork is immersed in liquid. example application: dry running protection of pumps The electronic switch opens if the limit is reached, if a fault occurs or in the event of a power fails (quiescent current principle) |
|
Supply: | ||
Rated voltage |
- DC-PNP: 10 ... 35 V DC, 3-wire - AC/DC: 20 ... 253 V AC/DC, 2-wire |
|
Current consumption |
- DC-PNP: < 15 mA - AC/DC: < 3.8 mA |
|
输入: | ||
Measured variable | density | |
Measurement range | min. 0.7 g/cm3, optional> 0.5 g/cm3 | |
输出: | ||
Output type | switch output | |
Switching current | max. 250 mA | |
指令符合: | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
符合: | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-64 | |
Climate class | DIN EN 60068-2-38/IEC 68-2-38 | |
测量精度: | ||
Reference operating conditions |
- ambient temperature: 25 °C (+77 °F) - process pressure: 1 bar (14.5 psi) - fluid: water (density: approx. 1 g/cm3, viscosity: 1 mm2/s) - medium temperature: 25 °C (+77 °F) - density setting: > 0.7 g/cm3 - switching time delay: standard (0,5 s, 1 s) |
|
Measured value resolution | < 0.5 mm | |
Measuring frequency | approx. 1100 Hz in air | |
Switching point | 13 mm ± 1 mm | |
Non-repeatability | ± 1 mm acc. to DIN 61298-2 | |
Hysteresis | max. 3 mm | |
Influence of ambient temperature | negligible | |
Influence of medium temperature | -25 µm/°C | |
Influence of medium pressure | -20 µm/bar | |
Switching time |
- 0.5 s when tuning fork is covered - 1.0 s when tuning fork is uncovered - other switching times on request |
|
操作条件: | ||
Installation conditions | ||
Installation position | see section mounting position | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Shock resistance | a = 300 m/s2 = 30 g, 3 planes x 2 directions x 3 shocks x 18 ms, as per test Ea | |
Vibration resistance | a(RMS) = 50 m/s2, ASD = 1.25 (m/s2)2/Hz, f = 5 to 2000 Hz, t = 3 x 2 h | |
Process conditions | ||
Medium temperature |
-40 ... +100 °C (-40 ... +212 °F) -40 ... +150 °C (-40 ... +302 °F) |
|
Process pressure (static pressure) | -1 ... +40 bar (-14.5 ... +580 psi) | |
State of aggregation | liquid | |
Density | min. 0.7 g/cm3, optional> 0.5 g/cm3 | |
Viscosity | 1 ... 10000 mPa/s, dynamic viscosity | |
Solid contents | < ∅5 mm | |
机械规格: | ||
Degree of protection |
- IP65/67, NEMA 4X enclosure (plug M12) - IP65, NEMA 4X enclosure (valve plug) - IP65/68, NEMA 4X/6P enclosure (cable) - IP66/68/69, NEMA 4X/6P Enclosure (M12 plug for metal housing cover) |
|
Connection |
- cable 5 m - valve plug NPT1/2 - valve plug QUICKON - valve plug M16 - plug M12 |
|
Material | see technical information (TI) | |
Surface quality |
Ra < 1.5 µm (EHEDG) Ra < 0.76 µm (EHEDG, 3-A) |
|
Mass | see technical information (TI) | |
Dimensions | see technical information (TI) | |
Process connection |
- thread ISO 228 G1/2, G3/4, G1 - DIN 11851 DN25 PN40, DN32 PN40, DN40 PN40 - thread ASME MNPT1/2, MNPT3/4, MNPT1 - thread M24 x 1,5 for flush-mounted installation in adapter - DIN 11851 DN25 PN40, DN32 PN40, DN40 PN40 (dairy pipe) - Tri-Clamp ISO 2852 DN25-38, DN40-51 - Flush-mounting in weld-in adapter Rd52, tuning fork can be aligned |
|
证书和批准: | ||
Sanitary compatibility | EHEDG , see approval (ZE) | |
Overspill protection |
Z-65.11-554 (overspill protection acc. to WHG) Z-65.40-555 (leak detection system acc. to WHG) If you need the approvals also in paper form, select the option WH in the type code. |
|
配件: | ||
Designation | see technical information (TI) |
上一篇:振动限位开关 LVL-A7