联系方式
联系人:王经理
 
电 话:021-39520660
 
手  机:15821591180
 
传 真:021-69001586
 
Q    Q:1257746205
 
Email:debon_gk@163.com
 

总线分配单元 KFD2-BR-Ex1.3PA.93

来源:未知    日期:2017/02/17    浏览量:


● Output: 12.6 ... 13.4 V/100 mA
● Couples PROFIBUS PA devices transparently to PROFIBUS DP
● Intrinsically safe, Ex ia (FISCO or Entity)
● Installation in Zone 2/Class I, Div. 2
● Fixed, high-availability terminator
● For all non-redundant masters
● Cyclic/acyclic data exchange


General specifications:
Design / Mounting Cabinet installation
Supply:
Connection Power Rail or terminals 59+, 60-, 58 FE
Rated voltage 20 ... 35 V DC
Ripple ≤ 10 %
Rated current 190 mA ... 430 mA
Fieldbus interface:
PROFIBUS PA  
  Connection terminals 3, 18+; 2, 17-
  Rated voltage 12.6 ... 13.4 V
  Rated current max. 100 mA
  Terminating impedance 100 Ω , integrated
PROFIBUS DP PROFIBUS with RS-485 transmission technology
  Connection Terminals 40 RxD/TxD-P, 41 RxD/TxD-N, 42 screen/FE, 55 DGND, 56 CNTR-P, 57 VP
  Baud rate 93.75 kBit/s
  Terminating impedance with rotary switch (S1) switchable: 1 = on; 0 = off
Galvanic isolation:
PROFIBUS DP/PROFIBUS PA safe galvanic isolation acc. to EN 50020, voltage peak value 375 V
PROFIBUS DP/Supply functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
PROFIBUS PA/Supply safe galvanic isolation acc. to EN 50020, voltage peak value 375 V
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013
Standard conformity:
Galvanic isolation EN 50178
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529
Fieldbus standard EN 50170/2
Climatic conditions IEC 60721
Ambient conditions:
Classification 3K3
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity < 75 %
Pollution degree max. 2, according to IEC 60664
Mechanical specifications:
Connection type Terminals
Core cross-section up to 2.5 mm2
Housing 100 mm x 115 mm x 107 mm
Degree of protection IP20
Mass 650 g
Mounting DIN rail mounting
Data for application in connection with hazardous areas:
EC-Type Examination Certificate PTB 99 ATEX 2142 , for additional certificates see www.pepperl-fuchs.com
  Group, category, type of protection, temperature class Ex-Hexagon II (1) G [Ex ia] IIC Ga , Ex-Hexagon II (1) D [Ex ia] IIIC Da
Supply  
  Maximum safe voltage 253 V AC / 125 V DC (Attention! Um is no rated voltage.)
PROFIBUS PA  
  Voltage 15 V
  Current 207.2 mA
  Power 1.93 W
  Maximum safe voltage 60 V
Statement of conformity PF 15 CERT 3527 X
  Group, category, type of protection, temperature class Ex-Hexagon II 3G Ex ec II T4 Gc
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012