来源:未知 日期:2017/06/09 浏览量:次
| Supply: | ||
|---|---|---|
| Rated voltage | 7.2 V DC , battery operated | |
| 电气特性: | ||
| Output rated operating current | 4 ... 20 mA | |
| Supply | 
				loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V  | 
		|
| 输入: | ||
| Connectable field devices | 
				usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode  | 
		|
| Connection | 
				terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode  | 
		|
| Current | 4 ... 20 mA | |
| HART communication | ||
| Protocol | HART 7.3, backward compatible | |
| Number of devices | 
				- one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode  | 
		|
| Transfer rate | 1200 Bit/s | |
| Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
| 输出: | ||
| Output variables | 
				PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables  | 
		|
| 传递特性: | ||
| Accuracy | current input: 0.125 % of measuring range | |
| Influence of ambient temperature | current input: 5 µA/K | |
| 指示灯/设置: | ||
| Parameter assignment | 
				- wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization  | 
		|
| 指令符合: | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013, CLASS A | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 2014/53/EU | EN 300328 V2.1.1:2017 , EN 301489-17 V3.1.1:2017 , EN 301489-1 V2.1.1:2017 | |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
| RoHs | ||
| Directive 2011/65/EU (RoHS) | EN 50581:2012 | |
| 符合: | ||
| Degree of protection | IEC 60529 | |
| 周围环境: | ||
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
| Corrosion resistance | 
				acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60  | 
		|
| 机械特性: | ||
| Degree of protection | IP66 | |
| Material | Aluminum | |
| Mass | approx. 1000 g | |
| Dimensions | 92 x 89.5 x 92.8 mm (without cable glands and antenna) | |
| Mounting | mounting on field device , panel or pole mounting | |
| 与危险区域有关的应用参数: | ||
| EU-Type Examination Certificate | BVS 17 ATEX E 029 | |
| Marking | 
				  II 2G Ex ia IIC T4/T3 Gb  II 2D Ex tb [ia] IIIC T70°C Db | 
		|
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2014 | |
| 国际认证: | ||
| CSA approval | ||
| Control drawing | 116-0435 | |
| IECEx approval | ||
| IECEx certificate | IECEX BVS 17.0023 | |
| 附件: | ||
| Designation | 
				battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-MKF8 threads (NPT 1/2", NPT 3/4", G 1/2, M20)  | 
		|