| Supply: | ||
|---|---|---|
| Rated voltage | 7.2 V DC , battery operated | |
| 电气规格: | ||
| Output rated operating current | 4 ... 20 mA | |
| Supply |
loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V |
|
| 输入: | ||
| Connectable field devices |
usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode |
|
| Connection |
terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode |
|
| Current | 4 ... 20 mA | |
| HART communication | ||
| Protocol | HART 7.1, backward compatible | |
| Number of devices |
- one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode |
|
| Transfer rate | 1200 Bit/s | |
| Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
| 输出: | ||
| Output variables |
PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables |
|
| Transfer characteristics: | ||
| Accuracy | current input: 0.125 % of measuring range | |
| Influence of ambient temperature | current input: 5 µA/K | |
| 指标/设置: | ||
| Parameter assignment |
- wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization |
|
| 指令符合: | ||
| Electromagnetic compatibility | ||
| Directive 2004/108/EC | EN 61326-1:2006 | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
| 符合: | ||
| Degree of protection | IEC 60529 | |
| 环境条件: | ||
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
| Corrosion resistance |
acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 |
|
| 机械规格: | ||
| Degree of protection | IP66 | |
| Material | aluminum | |
| Mass | approx. 1000 g | |
| Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 inch) (without cable glands and antenna) | |
| Mounting |
mounting on field device , panel or pole mounting versions see type code |
|
| 与危险区域有关的应用数据: | ||
| EC-Type Examination Certificate | BVS 11 ATEX E 081 , for additional certificates see www.pepperl-fuchs.com | |
| Group, category, type of protection, temperature class |
II 2 G Ex ia IIC T4 Gb II 2 D Ex tb [ia] IIIC T70°C Db IP6x |
|
| Directive conformity | ||
| Directive 94/9/EC | EN 60079-0:2009 , EN 60079-11:2007 , EN 60079-31:2009 | |
| 国际认证: | ||
| IECEx approval | BVS 11.0061 | |
| 配件: | ||
| Designation |
battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-MKF8 |
|