| Supply: | ||
|---|---|---|
| Rated voltage | 7 ... 30 V DC | |
| Rated current | < 1 mA , max. 25 mA | |
| Electrical specifications: | ||
| Output rated operating current | 3.2 ... 25 mA | |
| Supply |
loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V |
|
| Input: | ||
| Connection |
- 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point |
|
| HART communication | ||
| Protocol | HART 7.1, backward compatible | |
| Number of devices | up to 8 HART field devices (depending on installation) | |
| Directive conformity: | ||
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 2014/53/EU |
EN 300 328 V1.8.1:2012 EN 301 489-1 V1.9.2:2011 EN 301 489-17 V2.2.1:2012-09 |
|
| Conformity: | ||
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions: | ||
| Ambient temperature |
temperature class T5: -40 ... 85 °C (-40 ... 185 °F) temperature class T6: -40 ... 75 °C (-40 ... 167 °F) |
|
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications: | ||
| Degree of protection | IP67 | |
| Material | Aluminum alloy with polyurethane enamel paint | |
| Mass | 460 g | |
| Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
| Data for application in connection with hazardous areas: | ||
| EC-Type Examination Certificate | FM 11 ATEX 0019 X | |
| Group, category, type of protection, temperature class |
II 1 G Ex ia IIC T6/T5 Ga II 1 D Ex ia IIIC T95 °C Da |
|
| Statement of conformity | FM 11 ATEX 0068 X | |
| Group, category, type of protection |
II 3 G Ex nA IIC T6/T5 Gc |
|
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals: | ||
| FM approval | CoC3040786(C) | |
| Approved for |
Class I, Zone 0, (A)Ex ia IIC T6/T5 Ga Class I, Zone 2, (A)Ex nA IIC T6/T5 Gc Class I, Zone 20, (A)Ex ia IIIC T95°C Da Class I, Division 1, Groups A - D Class II, Division 1, Groups E - G Class III Class I, Division 2, Groups A - D |
|
| IECEx approval | IECEx FMG 11.0010X | |
| Approved for |
Ex ia IIC T6/T5 Ga Ex nA IIC T6/T5 Gc Ex ia IIIC T95°C Da |
|
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 , IEC 60079-15:2010 | |
上一篇:没有了