联系方式
联系人:王经理
 
电 话:021-39520660
 
手  机:15821591180
 
传 真:021-69001586
 
Q    Q:1257746205
 
Email:debon_gk@163.com
 

无线温度转换器 WHA-UT-F7B1-0-PP-Z1-Ex2

来源:未知    日期:2017/02/21    浏览量:


● 2-channel
● Installation in Zone 1
● WirelessHART converter
● Battery operated
● Thermocouple or RTD input
● Output WirelessHART wireless interface
● Internal antenna


Supply:
Rated voltage 3.6 V DC , battery operated
Power dissipation/power consumption < 0.09 W
Input:
Connection terminals 1, 2, 3, 4
RTD type Pt100, Pt1000 (IEC 751: 1995; GOST: alpha = 0.391)
  Connection 2-wire: 2 sensors, 3- or 4-wire: 1 sensor
  Lead resistance max. 10 Ω
  Measuring circuit monitoring sensor breakage
Thermocouples type E, J, K, T (IEC 584-1)
  Cold junction compensation internal , external
  Measuring circuit monitoring sensor breakage
  Measurement range type K: -270 ... 1370 °C
type T: -270 ... 400 °C
type E: -270 ... 1000 °C
type J: -210 ... 1200 °C
Resistor  
  Measurement range 0 ... 500 Ω , 0 ... 4000 Ω
Voltage mV Input
  Measurement range -100 ... 100 mV , 0 ... 300 mV
Input resistance ≥ 1 MΩ
Output:
Output variables PV: input 1 (°C, Ω, mV)
SV: input 2 (°C, Ω, mV)
TV: CJC temperature (°C)
estimated battery life (days)
battery voltage (volts)
residual battery capacity (%)
Transfer characteristics:
Accuracy - internal cold junction compensation error ± 1,5 °C (typ. acc. to IEC 61298-3)
- external cold junction compensation error ± 1 °C (typ.)
- resolution error < 0.1 °C
- accuracy TC ± 20 µV
- accuracy RTD: ± 100 mΩ
Indicators/settings:
Parameter assignment - sampling period: 1, 2, 5, 10, 30 seconds or 1, 2, 5, 10, 30, 60 minutes
- transmit power: configurable 0 dBm or 10 dBm (EIRP)
- sensor type
- mapping of input measuring values 1 and 2 into primary variable (PV) and secondary variable (SV)
- publishing of up to three messages from the device, transmission rate selectable from 4 seconds to 60 minutes
Directive conformity:
Electromagnetic compatibility  
  Directive 2004/108/EC EN 61326-1:2006
Radio and telecommunication terminal equipment The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning.
  Directive 99/5/EC ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001
  FCC CFR47 Part 15 B and C ANSI C63.4-2003
Conformity:
Degree of protection IEC 60529
Accuracy IEC 61298-3
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -20 ... 70 °C (-4 ... 158 °F)
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
test setup and execution acc. to EN 60068-2-60
Mechanical specifications:
Degree of protection IP65
Mass approx. 1000 g
Dimensions 77 x 129 x 177 mm (3 x 5.08 x 6.97 inch)
Mounting panel or pole mounting
Data for application in connection with hazardous areas:
EC-Type Examination Certificate IMQ 09 ATEX 008X
  Group, category, type of protection Ex-Hexagon II 2(1)G Ex ia [ia] IIC T4
Directive conformity  
  Directive 94/9/EC EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007
International approvals:
FM approval CoC 3042534
IECEx approval IECEx INE 09.0025X
  Approved for Ex ia IIC T4
Accessories:
Designation battery W-BAT-B1-Li mandatory for use in connection with hazardous areas (order separately)
Mounting set W-ACC-F7MK
External cold junction compensation W-ACC-CJC

上一篇:没有了