联系方式
联系人:王经理
 
电 话:021-39520660
 
手  机:15821591180
 
传 真:021-69001586
 
Q    Q:1257746205
 
Email:debon_gk@163.com
 

无线网关 WHA-GW-F2D2-0-A*-Z2-ETH

来源:未知    日期:2017/02/16    浏览量:


● MODBUS WirelessHART Gateway
● Graphical network analysis
● Simple and automatic configuration options
● Ethernet and RS 485 interface
● HART and MODBUS protocol via both interfaces
● Input WirelessHART wireless interface
● 24 V DC supply
● Redundant power supply connections


Supply:
Rated voltage 20 ... 30 V DC SELV/PELV
Power consumption < 5 W
External bus:
Connection screw terminals for
- 0.2 ... 4 mm2 (rigid wire)
- 0.2 ... 2.5 mm2 (flexible wire)
Interface 1 Ethernet
10 BASE-T/100 BASE-TX , full galvanic isolation
  Protocol HART UDP, MODBUS TCP
Interface 2 RS-485
  Protocol HART, MODBUS RTU
  Transfer rate max. 115 kBit/s
Galvanic isolation:
Interface/interface basic insulation according to IEC 61140, rated insulation voltage 50 Veff
Directive conformity:
Electromagnetic compatibility  
  Directive 2004/108/EC EN 61326-1:2006
Radio and telecommunication terminal equipment The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning.
  Directive 99/5/EC EN 300328: V1.7.1
EN 301489-17: V1.3.2
  FCC CFR47 Part 15 B and C ANSI C63.4-2003
Conformity:
Degree of protection IEC 60529
Ambient conditions:
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
test setup and execution acc. to EN 60068-2-60
Mechanical specifications:
Degree of protection IP66/IP67
Mass approx. 1 kg
Dimensions 258 mm x 114 mm x 84 mm
without antenna and cable glands
Mounting panel mounting
Data for application in connection with hazardous areas:
EC-Type Examination Certificate FM 12 ATEX 0061 , for additional certificates see www.pepperl-fuchs.com
  Group, category, type of protection, temperature class Ex-Hexagon II 3 G Ex nA nC IIC T4 Gc
Directive conformity  
  Directive 94/9/EC EN 60079-0:2012
EN 60079-15:2010
International approvals:
FM approval Coc3042646
  Approved for NI Class I, Div. 2, GPS A-D
NI Class II, Class III, Div. 2, GPS E-G
IECEx approval IECEx FMG 12.0002
  Approved for Ex nA nC IIC T4 Gc
Ex nAc nCc T4

上一篇:没有了
下一篇:无线网关 WHA-GW-F2D2-0-A*-Z2-ETH.EIP