来源:未知 日期:2018/04/18 浏览量:次
| 产品阐述: | ||
|---|---|---|
|
Input 0/4 mA ... 20 mA 2 x Output 0/4 mA ... 20 mA |
||
| 一般特性: | ||
|---|---|---|
| Signal type | Analog input | |
| 功能安全相关参数: | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply: | ||
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | 18 ... 30 V DC | |
| Ripple | within the supply tolerance | |
| Power dissipation | approx. 1.4 W at 20 mA transfer current, 250 Ω in both outputs | |
| Power consumption | 2 W | |
| 输入: | ||
| Connection side | field side | |
| Connection | terminals 1+, 2- (sink); 3+, 4- (source) | |
| Input signal | 0/4 ... 20 mA | |
| Voltage drop | terminals 3, 4: ≤ 6.1 V at 20 mA | |
| Short-circuit current | terminals 1+, 2-: 25 mA | |
| Input resistance |
terminals 1+, 2-: max. 500 Ω (250 Ω load) |
|
| Available voltage | terminals 1+, 2-: ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA | |
| 输出: | ||
| Connection side | control side | |
| Connection |
source: terminals 5-, 6+; 7-, 8+ sink: terminals 5+, 6-, 7+, 8- |
|
| Load |
channel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V) channel 2: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V) |
|
| Output signal | 0/4 ... 20 mA or 0/1 ... 5 V | |
| Ripple | max. 50 µA rms | |
| 传递特性: | ||
| Deviation | Iout < 20 µA (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V | |
| Influence of ambient temperature |
current output: 0.25 µA/K voltage output: 80 µV/K |
|
| Frequency range |
field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB) |
|
| Settling time | 6 ms | |
| Rise time/fall time | 2 ms | |
| 电流隔离: | ||
| Output/power supply | functional insulation, rated insulation voltage 50 V AC | |
| Output/Output | functional insulation, rated insulation voltage 50 V AC | |
| 指示灯/设置: | ||
| Display elements | LED | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| 指令符合: | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| 符合: | ||
| Electromagnetic compatibility |
NE 21:2012 EN 61326-3-2:2008 |
|
| Degree of protection | IEC 60529:2001 | |
| Protection against electrical shock | UL 61010-1:2012 | |
| 周围环境: | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| 机械特性: | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 114 x 122 mm (0.5 x 4.5 x 4.8 inch) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| 与危险区域性应用参数: | ||
| EU-Type Examination Certificate | BASEEFA 13 ATEX 0077 X | |
| Marking |
II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
| Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Supply | ||
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
| Equipment | terminals 1+, 2- | |
| Voltage Uo | 25.2 V | |
| Voltage Uq | 28.2 V | |
| Current Io | 93 mA | |
| Power Po | 656 mW | |
| Equipment | terminals 3+, 4- | |
| Voltage Ui | 30 V | |
| Current Ii | 115 mA | |
| Power Pi | 700 mW | |
| Voltage Uo | 5 V | |
| Current Io | 6.8 mA | |
| Power Po | 1.6 mW | |
| Output | ||
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
| Certificate | BASEEFA 13 ATEX 0078 X | |
| Marking |
II 3G Ex nA II T4 Gc [device in zone 2] |
|
| Galvanic isolation | ||
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| 国际认证: | ||
| UL approval | ||
| Control drawing | 116-0380 (cULus) | |
| IECEx approval | IECEx BAS 13.0043X | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| 一般信息: | ||
| Note | Both output loads must be connected to ensure complete and correct operation within the technical specification. | |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |