一般特性: | ||
---|---|---|
Signal type | Analog output | |
功能安全相关参数: | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply: | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 1.1 W at 20 mA into 10 V (equivalent to 500 Ω) load | |
Power consumption | 1.3 W | |
输入: | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Voltage drop | approx. 4 V or internal resistance 200 Ω at 20 mA | |
Input resistance | > 100 kΩ, when wiring resistance in the field < 50 Ω or > 800 Ω at 20 mA | |
Current | 4 ... 20 mA limited to approx. 25 mA | |
输出: | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current | 4 ... 20 mA | |
Load | 100 ... 700 Ω | |
Voltage | ≥ 14 V at 20 mA | |
传递特性: | ||
Accuracy | 0.1 % | |
Rise time | < 100 µs at bounce from 10 ... 90 % | |
指示灯/设置: | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
指令符合: | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
符合: | ||
Insulation coordination | EN 50178:1997 | |
Galvanic isolation | EN 50178:1997 | |
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
周围环境: | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
机械特性: | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 115 x 115 mm (0.8 x 4.5 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
在危险区域连接的应用程序数据: | ||
EU-Type Examination Certificate | BAS 00 ATEX 7215 | |
Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | II 3G Ex nA II T4 [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
国际认证: | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
IECEx approval | IECEx BAS 16.0045 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |