来源:未知 日期:2017/08/07 浏览量:次
| 一般特性: | ||
|---|---|---|
| Signal type | Digital Input | |
| Supply: | ||
| Connection | Power Rail or terminals 14+, 15- | |
| Rated voltage | 20 ... 30 V DC | |
| Ripple | ≤ 10 % | |
| Rated current | ≤ 50 mA | |
| Power dissipation | 1 W | |
| Power consumption | < 1.3 W | |
| 输入: | ||
| Connection | terminals 1+, 2+, 3- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA | |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
| 输出: | ||
| Connection | output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 | |
| Output I | signal ; relay | |
| Output II | signal or error message ; relay | |
| Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
| Minimum switch current | 2 mA / 24 V DC | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Mechanical life | 107 switching cycles | |
| 传递特性: | ||
| Switching frequency | ≤ 10 Hz | |
| 指令符合: | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| 符合: | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| 周围环境: | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| 机械特性: | ||
| Degree of protection | IP20 | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| 与危险区域有关的应用数据: | ||
| EC-Type Examination Certificate | PTB 00 ATEX 2080 | |
| Group, category, type of protection |
II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
| Error message output | ||
| Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
| Statement of conformity | PF 08 CERT 0803 | |
| Group, category, type of protection |
II (3)G [Ex ic Gc] IIC |
|
| Statement of conformity | TÜV 99 ATEX 1493 X | |
| Group, category, type of protection, temperature class |
II 3G Ex nA nC IIC T4 |
|
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| 国际认证: | ||
| FM approval | ||
| Control drawing | 116-0035 | |
| CSA approval | ||
| Control drawing | 116-0047 | |
| IECEx approval | IECEx PTB 11.0034 | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |