来源:未知 日期:2017/08/07 浏览量:次
一般特性: | ||
---|---|---|
Signal type | Digital Input | |
Supply: | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | ≤ 30 mA | |
Power dissipation | ≤ 600 mW | |
Power consumption | ≤ 600 mW | |
输入: | ||
Connection | terminals 1+, 2-; 3+, 4- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
输出: | ||
Connection | terminals 5, 6; 7, 8 | |
Output I | signal ; relay | |
Output II | signal ; relay | |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms | |
Mechanical life | 107 switching cycles | |
传递特性: | ||
Switching frequency | ≤ 10 Hz | |
指令符合: | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
符合: | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529:2001 | |
周围环境: | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
机械特性: | ||
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
在危险区域连接的应用程序数据: | ||
EU-Type Examination Certificate | BASEEFA 06 ATEX 0092 | |
Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I | |
Certificate | PF 06 CERT 0972 X | |
Marking | II 3G Ex nA nC IIC T4 Gc | |
Output I, II | ||
Contact loading | 50 V AC/2 A/cos φ > 0.7; 30 V DC/2 A resistive load | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
国际认证: | ||
FM approval | ||
Control drawing | 116-0419 (cFMus) | |
UL approval | ||
Control drawing | 116-0420 (cULus) | |
IECEx approval | IECEx BAS 06.0025 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |