| 一般特性: | ||
|---|---|---|
| Signal type | Analog input | |
| Supply: | ||
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | 19 ... 30 V DC | |
| Ripple | within the supply tolerance | |
| Rated current | < 20 mA | |
| Power consumption | 0.35 W (24 V and 1 mA sense current) | |
| 输入: | ||
| Connection | terminals 1, 2, 3, 4 | |
| Line fault detection | yes , at Pt100 | |
| Lead resistance | ≤ 10 % of resistance value | |
| Transmission range | 0 ... 10 mA | |
| Available voltage | 9 V | |
| Line fault detection | 8 nA | |
| 输出: | ||
| Connection | terminals 5-, 7-, 6+, 8+ | |
| Current | 0 ... 10 mA | |
| Available voltage | 0 ... 4.2 V | |
| Fault signal |
< 10 Ω or > 400 Ω, depending on lead disconnected (measuring current ≤ 1 mA) > 400 Ω, terminal 3 lead disconnected in 2-/4-wire (measuring current ≤ 0.3 mA) |
|
| 传递特性: | ||
| Deviation |
4-wire Im ≥ 1 mA: ±0.1 % of Rm or ± 0.1 Ω (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 Ω (the larger value is applicable). 3-wire Im ≥ 1 mA: (±0.1 % - 0.1 Ω Offset) or ± 0.2 Ω (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: (±1 % - 0.1 Ω Offset) or ± 1.1 Ω (the larger value is applicable) |
|
| Rise time |
signal response time ≤ 2 ms (10 ... 90 %) response to application of Im: Rm > 50 Ω and Im < 5mA: < 5ms response to application of Im: Rm > 30 Ω and Im < 5mA: < 10ms response to application of Im: Rm > 18 Ω and Im < 5mA: < 20ms |
|
| 指令符合: | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| 符合: | ||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529:2001 | |
| 周围环境: | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| 机械特性: | ||
| Degree of protection | IP20 | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| 与危险区域性应用参数: | ||
| EU-Type Examination Certificate | BASEEFA 10 ATEX 0061 | |
| Marking |
II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
| Certificate | BASEEFA 10 ATEX 0062X | |
| Marking |
II 3G Ex nA II T4 Gc [device in zone 2] |
|
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| 国际认证: | ||
| FM approval | ||
| Control drawing | 116-0129 (cFMus) | |
| UL approval | ||
| Control drawing | 116-0332 (cULus) | |
| IECEx approval |
IECEx BAS 10.0024 IECEx BAS 10.0025X |
|
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| 附件: | ||
| Designation | optional accessories: insertion bridge EBP 2- 5 | |