现场总线电源 KLD2-FBPS-1.25.360

来源:未知    日期:2017/02/22    浏览量:


● Output: 25 ... 27 V/360 mA
● For most fieldbus applications
● High-power trunk for high device count and long cable lengths
● Installation in Zone 2/Class I, Div. 2
● For FOUNDATION Fieldbus H1
● Fixed, high-availability terminator
● No spacing required between modules


General specifications:
Design / Mounting Cabinet installation
Supply:
Connection Power Rail or terminals 8+, 11+; 9-, 12-
Rated voltage 19.2 ... 35 V DC
Rated current 630 ... 340 mA
Power dissipation typ. 2,0 W
Fieldbus interface:
Connection terminals 3+, 6+; 2-, 5-; 1S, 4S (S=screen connection)
Rated voltage 25 ... 27 V
Rated current 360 mA
Galvanic isolation:
Fieldbus segment/Supply functional insulation acc. to IEC 62103, rated insulation voltage 250 V AC
Directive conformity:
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013
Standard conformity:
Electromagnetic compatibility NE 21:2006
Degree of protection IEC/EN 60529
Fieldbus standard IEC 61158-2, ISA S 50.02 part 2
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions:
Ambient temperature -40 ... 60 °C (-40 ... 140 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity < 95 % non-condensing
Shock resistance 15 g 11 ms
Vibration resistance 1 g , 10 ... 150 Hz
Pollution degree max. 2, according to IEC 60664
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications:
Connection type Terminals
Core cross-section up to 2.5 mm2
Housing 20 mm x 115 mm x 107 mm
Housing material Polycarbonate
Degree of protection IP20
Mass approx. 210 g
Mounting DIN rail mounting
Data for application in connection with hazardous areas:
Statement of conformity TÜV 06 ATEX 553079 X
  Group, category, type of protection, temperature class Ex-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012 , EN 60079-7:2015
International approvals:
FM approval CoC 3024816, CoC 3024816C
  Approved for Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex nA IIC T4
Certificates and approvals:
Marine approval DNV A-14038